Assessment Year | 2000 |
---|---|
Principal Product | concrete fasteners |
NAICS |
n/a
|
SIC | 3452: Bolts, Nuts, Screws, Rivets, and Washers |
Sales Range | $10 M to 50M |
# of Employees | 59 |
Plant Area |
60,000
ft2
|
Annual Production | 0
units
|
Production Hrs. Annual | 6,120
hrs
|
Location (State) | Indiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $105,877 | 1,757,913 |
kWh
|
$0.060 |
Electricity Demand | $58,978 | 5,778 |
kW-mo/yr
|
$10.21 |
Natural Gas | $29,179 | 5,453 |
MMBtu
|
$5.35 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $11,274 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $2,250 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.7111: Reduce illumination to minimum necessary levels | $6,569 | $600 |
$4,911
81,477
kWh
|
$1,658
-
kW-mo/yr
|
|
02 | 2.7135: Install occupancy sensors | $1,894 | $600 |
$1,409
23,447
kWh
|
$485
-
kW-mo/yr
|
|
03 | 2.4221: Install compressor air intakes in coolest locations | $561 | $350 |
$422
7,034
kWh
|
$139
-
kW-mo/yr
|
|
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,250 | $160 | - |
$2,250
-
kW-mo/yr
|
|
TOTAL RECOMMENDED | $11,274 | $1,710 |
$6,742
111,958
kWh
|
$4,532
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $2,250 | $160 | - |
$2,250
-
kW-mo/yr
|
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs