ITAC Assessment: ND0327
ITAC logo
ITAC Assessment: ND0327
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 1999
Principal Product Plastic Auto Parts
NAICS
n/a
SIC 3089: Plastics Products, Not Elsewhere Classified
Sales Range $10
M
to 50
M
# of Employees 225
Plant Area 70,000
ft2
Annual Production 1,000,000
pieces
Production Hrs. Annual 7,488
hrs
Location (State) Indiana

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $394,989 8,056,858
kWh
Electricity Demand $272,450 17,999
kW-mo/yr
Natural Gas $36,742 5,968
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $40,552 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $36,278

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Water Disposal Savings Personnel Changes Savings Administrative Changes Savings Ancillary Material Cost Savings
01 2.2614: Use cooling tower or economizer to replace chiller cooling $17,546 $25,000 $10,105
946,366
kWh
$8,641
-
kW-mo/yr
- - $(-1,200.0) - -
02 2.7144: Install spectral reflectors / delamp $1,497 $240 $422
39,566
kWh
$1,075
-
kW-mo/yr
- - - - -
03 2.4221: Install compressor air intakes in coolest locations $1,029 $1,500 $290
27,257
kWh
$739
-
kW-mo/yr
- - - - -
04 2.2511: Insulate bare equipment $744 $1,392 $744
69,754
kWh
- - - - - -
05 2.1311: Replace electrically-operated equipment with fossil fuel equipment $564 $420 $81
7,620
kWh
$683
-
kW-mo/yr
$(-200.0)
-
MMBtu
- - - -
06 2.7142: Utilize higher efficiency lamps and/or ballasts $140 $315 $19
1,758
kWh
$41
-
kW-mo/yr
- - - - $80
07 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $105 $120 $105
9,672
kWh
- - - - - -
08 3.4151: Minimize water usage $510 $1,150 - - - $504
-
Tgal
$100 - $(-94.0)
09 4.454: Modify startup/shutdown times $16,882 - - $19,222
-
kW-mo/yr
- - $(-2,340.0) - -
10 4.821: Pay bills on time to avoid late fees $1,106 - - - - - - $1,106 -
11 4.611: Begin a practice of predictive / preventative maintenance $429 - - - - - $429 - -
TOTAL RECOMMENDED $40,552 $30,137 $11,766
1,101,993
kWh
$30,401
-
kW-mo/yr
$(-200.0)
-
MMBtu
$504
-
Tgal
$(-3,011.0) $1,106 $(-14.0)
TOTAL IMPLEMENTED $36,278 $26,392 $10,849
1,016,120
kWh
$27,863
-
kW-mo/yr
- - $(-3,540.0) $1,106 -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Water Disposal Savings Personnel Changes Savings Administrative Changes Savings Ancillary Material Cost Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs