ITAC Assessment: ND0326
ITAC logo
ITAC Assessment: ND0326
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 1999
Principal Product Foundry
NAICS
n/a
SIC 3321: Gray and Ductile Iron Foundries
Sales Range $100
M
to 500
M
# of Employees 820
Plant Area 292,000
ft2
Annual Production 100,000
ton
Production Hrs. Annual 8,424
hrs
Location (State) Indiana

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $1,783,408 60,569,755
kWh
Electricity Demand $677,171 37,400
kW-mo/yr
Natural Gas $736,807 239,377
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $233,679 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $258

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Personnel Changes Savings Ancillary Material Cost Savings Water Consumption Savings
01 2.2442: Preheat combustion air with waste heat $214,338 $180,000 $(-1,779.0)
(-60,375)
kWh
$(-1,559.0)
-
kW-mo/yr
$217,676
-
MMBtu
- - -
02 2.7142: Utilize higher efficiency lamps and/or ballasts $126 $160 $39
1,465
kWh
$33
-
kW-mo/yr
- - $54 -
03 2.4221: Install compressor air intakes in coolest locations $11,257 $2,000 $10,317
350,528
kWh
$940
-
kW-mo/yr
- - - -
04 2.6218: Turn off equipment when not in use $60 $87 $60
2,052
kWh
- - - - -
05 2.7111: Reduce illumination to minimum necessary levels $198 $40 $149
4,982
kWh
$130
-
kW-mo/yr
- - $(-81.0) -
06 2.3134: Shift from daytime to nighttime operation $6,520 $14,100 - $6,520
-
kW-mo/yr
- - - -
07 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $568 $1,800 $409
13,775
kWh
$239
-
kW-mo/yr
- $(-80.0) - -
08 3.4151: Minimize water usage $912 $1,760 - - - - - $912
-
Tgal
09 2.7142: Utilize higher efficiency lamps and/or ballasts $(-300.0) $1,118 $132
4,396
kWh
$308
-
kW-mo/yr
- $(-740.0) - -
TOTAL RECOMMENDED $233,679 $201,065 $9,327
316,823
kWh
$6,611
-
kW-mo/yr
$217,676
-
MMBtu
$(-820.0) $(-27.0) $912
-
Tgal
TOTAL IMPLEMENTED $258 $127 $209
7,034
kWh
$130
-
kW-mo/yr
- - $(-81.0) -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Personnel Changes Savings Ancillary Material Cost Savings Water Consumption Savings