| Assessment Year | 1998 |
|---|---|
| Principal Product | Printed Sheets for Aerosol Cans |
| NAICS |
n/a
|
| SIC | 2796: Platemaking and Related Services |
| Sales Range | $10 M to 50M |
| # of Employees | 140 |
| Plant Area |
190,000
ft2
|
| Annual Production | 98,000,000
pieces
|
| Production Hrs. Annual | 6,384
hrs
|
| Location (State) | Indiana |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $435,130 | 10,740,328 |
kWh
|
$0.041 |
| Natural Gas | $594,320 | 206,736 |
MMBtu
|
$2.87 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $113,360 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $94,720 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings | Primary Raw Material Savings | By-product Production Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.7442: Keep doors and windows shut when not on use | $9,419 | $24,900 | - |
$9,419
-
MMBtu
|
- | - | - | |
| 02 | 2.7243: Improve air circulation with destratification fans / other methods | $27,164 | $9,600 |
$(-233.0)
(-5,862)
kWh
|
$27,397
-
MMBtu
|
- | - | - | |
| 03 | 2.7226: Use computer programs to optimize hvac performance | $56,650 | $65,000 | - | - | - | $56,650 | - | |
| 04 | 2.7291: Reschedule and rearrange multiple-source heating systems | $1,487 | - | - |
$1,487
-
MMBtu
|
- | - | - | |
| 05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,890 | $8,263 |
$1,890
46,307
kWh
|
- | - | - | - | |
| 06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $501 | $880 |
$217
5,275
kWh
|
- | $284 | - | - | |
| 07 | 2.7135: Install occupancy sensors | $1,001 | $600 |
$1,001
24,619
kWh
|
- | - | - | - | |
| 08 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $60 | $200 |
$83
2,052
kWh
|
$(-23.0)
-
MMBtu
|
- | - | - | |
| 09 | 2.6121: Reduce hot water temperature to the minimum required | $2 | - |
$2
293
kWh
|
- | - | - | - | |
| 10 | 2.1332: Convert combustion equipment to burn natural gas | $15,186 | $42,730 | - | - | - | - | $15,186 | |
| TOTAL RECOMMENDED | $113,360 | $152,173 |
$2,960
72,684
kWh
|
$38,280
-
MMBtu
|
$284 | $56,650 | $15,186 | ||
| TOTAL IMPLEMENTED | $94,720 | $99,500 |
$(-233.0)
(-5,862)
kWh
|
$38,303
-
MMBtu
|
- | $56,650 | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings | Primary Raw Material Savings | By-product Production Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs