Assessment Year 2006
Principal Product Specialty plating chemicals
NAICS 325180: Other Basic Inorganic Chemical Manufacturing
SIC 2819: Industrial Inorganic Chemicals, Not Elsewhere Classified
Sales Range $1
M
to 5
M
# of Employees 50
Plant Area 100,000
ft2
Annual Production 36,000,000
lb
Production Hrs. Annual 6,000
hrs
Location (State) South Carolina

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $220,134 6,543,076
kWh
Electricity Demand $144,422 13,696
kW-mo/yr
Natural Gas $212,228 18,096
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $22,723 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $291

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings
01 2.2622: Replace existing chiller with high efficiency model $8,498 $4,000 $5,725
177,903
kWh
$2,773
-
kW-mo/yr
-
02 2.4226: Use / purchase optimum sized compressor $2,488 $8,000 $2,488
77,308
kWh
- -
03 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $3,461 $4,000 $2,147
66,735
kWh
- $1,314
-
MMBtu
04 2.7142: Utilize higher efficiency lamps and/or ballasts $6,300 $50 $4,428
137,600
kWh
$1,872
-
kW-mo/yr
-
05 2.7142: Utilize higher efficiency lamps and/or ballasts $1,538 $2,465 $656
20,394
kWh
$882
-
kW-mo/yr
-
06 2.7134: Use photocell controls $147 $95 $54
1,664
kWh
$93
-
kW-mo/yr
-
07 2.7134: Use photocell controls $291 $95 $130
4,030
kWh
$161
-
kW-mo/yr
-
TOTAL RECOMMENDED $22,723 $18,705 $15,628
485,634
kWh
$5,781
-
kW-mo/yr
$1,314
-
MMBtu
TOTAL IMPLEMENTED $291 $95 $130
4,030
kWh
$161
-
kW-mo/yr
-
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs