| Assessment Year | 1998 |
|---|---|
| Principal Product | Screw Machine Products |
| NAICS |
n/a
|
| SIC | 3451: Screw Machine Products |
| Sales Range | $1 M to 5M |
| # of Employees | 30 |
| Plant Area |
25,000
ft2
|
| Annual Production | 6,500,000
pieces
|
| Production Hrs. Annual | 4,896
hrs
|
| Location (State) | Indiana |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $33,321 | 705,451 |
kWh
|
$0.047 |
| Electricity Demand | $10,149 | 2,378 |
kW-mo/yr
|
$4.27 |
| Electricity Fees | $303 | - |
|
- |
| Natural Gas | $2,743 | 472 |
MMBtu
|
$5.81 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $17,218 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $972 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Solid Waste (non-haz) Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.4133: Use most efficient type of electric motors | $9,033 | $9,050 |
$7,286
116,647
kWh
|
$1,747
-
kW-mo/yr
|
- | - | - | |
| 02 | 2.2515: Use optimum thickness insulation | $3,747 | $7,563 | - | - | - |
$3,747
-
MMBtu
|
- | |
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,152 | $939 |
$2,152
34,584
kWh
|
- | - | - | - | |
| 04 | 2.7135: Install occupancy sensors | $453 | $1,200 |
$453
7,327
kWh
|
- | - | - | - | |
| 05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $345 | $80 |
$345
5,569
kWh
|
- | - | - | - | |
| 06 | 3.5316: Contract a wood pallet recycling company | $315 | $60 | - | - | - | - |
$315
-
lb
|
|
| 07 | 2.4221: Install compressor air intakes in coolest locations | $287 | $60 |
$287
6,741
kWh
|
- | - | - | - | |
| 08 | 2.8114: Change rate schedules or other changes in utility service | $280 | $1,200 | - | - | $280 | - | - | |
| 09 | 2.2515: Use optimum thickness insulation | $260 | $398 | - | - | - |
$260
-
MMBtu
|
- | |
| 10 | 2.7124: Make a practice of turning off lights when not needed | $189 | - |
$189
2,931
kWh
|
- | - | - | - | |
| 11 | 4.821: Pay bills on time to avoid late fees | $123 | - | - | - | $123 | - | - | |
| 12 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $34 | $65 |
$34
293
kWh
|
- | - | - | - | |
| TOTAL RECOMMENDED | $17,218 | $20,615 |
$10,746
174,092
kWh
|
$1,747
-
kW-mo/yr
|
$403 |
$4,007
-
MMBtu
|
$315
-
lb
|
||
| TOTAL IMPLEMENTED | $972 | $140 |
$534
8,500
kWh
|
- | $123 | - |
$315
-
lb
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Solid Waste (non-haz) Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs