ITAC Assessment: ND0265
ITAC logo
ITAC Assessment: ND0265
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 1996
Principal Product Vacuum Formed Plastic
NAICS
n/a
SIC 3089: Plastics Products, Not Elsewhere Classified
Sales Range $5
M
to 10
M
# of Employees 50
Plant Area 60,000
ft2
Annual Production 1,000,000
lb
Production Hrs. Annual 4,290
hrs
Location (State) Indiana

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $101,648 1,345,252
kWh
Electricity Demand $37,813 1,707
kW-mo/yr
Natural Gas $9,653 2,445
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $83,107 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $2,267

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Other Liquid (non-haz) Savings
01 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $1,007 $80 $1,007
13,189
kWh
- - -
02 2.4221: Install compressor air intakes in coolest locations $914 $200 $914
12,016
kWh
- - -
03 2.7142: Utilize higher efficiency lamps and/or ballasts $232 $360 $232
2,931
kWh
- - -
04 2.7142: Utilize higher efficiency lamps and/or ballasts $386 $527 $242
3,224
kWh
$144
-
kW-mo/yr
- -
05 2.6218: Turn off equipment when not in use $109 $504 $109
2,345
kWh
- - -
06 2.4133: Use most efficient type of electric motors $642 $3,360 $403
5,275
kWh
$239
-
kW-mo/yr
- -
07 2.7135: Install occupancy sensors $590 $1,400 $590
7,620
kWh
- - -
08 2.1311: Replace electrically-operated equipment with fossil fuel equipment $76,364 $56,397 $92,309
1,201,348
kWh
- $(-15,945.0)
-
MMBtu
-
09 2.4111: Utilize energy-efficient belts and other improved mechanisms $1,638 $80 $1,638
21,395
kWh
- - -
10 3.2123: Convert to high volume low pressure (hvlp) paint guns $1,225 $200 - - - $1,225
-
gal
TOTAL RECOMMENDED $83,107 $63,108 $97,444
1,269,343
kWh
$383
-
kW-mo/yr
$(-15,945.0)
-
MMBtu
$1,225
-
gal
TOTAL IMPLEMENTED $2,267 $4,327 $1,884
24,619
kWh
$383
-
kW-mo/yr
- -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Other Liquid (non-haz) Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs