Assessment Year 1996
Principal Product Mobile Homes
NAICS
n/a
SIC 2451: Mobile Homes
Sales Range $10
M
to 50
M
# of Employees 100
Plant Area 80,000
ft2
Annual Production 477
pieces
Production Hrs. Annual 2,210
hrs
Location (State) Indiana

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $45,520 736,811
kWh
Electricity Demand $22,760 2,842
kW-mo/yr
Electricity Fees $(-4,495.0) -
Natural Gas $29,844 8,691
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $7,245 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $6,232

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Solid Waste (non-haz) Savings
01 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $2,345 $400 $2,345
38,101
kWh
- - -
02 2.4221: Install compressor air intakes in coolest locations $204 $200 $204
3,224
kWh
- - -
03 2.4133: Use most efficient type of electric motors $167 $315 $111
1,758
kWh
$56
-
kW-mo/yr
- -
04 2.2437: Recover waste heat from equipment $207 $100 - - $207
-
MMBtu
-
05 2.7142: Utilize higher efficiency lamps and/or ballasts $230 $141 $153
1,758
kWh
$77
-
kW-mo/yr
- -
06 2.7491: Insulate glazing, walls, ceilings, and roofs $372 $720 - - $372
-
MMBtu
-
07 3.5313: Increase amount of waste recovered for resale $1,020 $480 - - - $1,020
-
lb
08 3.5313: Increase amount of waste recovered for resale $2,700 $480 - - - $2,700
-
lb
TOTAL RECOMMENDED $7,245 $2,836 $2,813
44,841
kWh
$133
-
kW-mo/yr
$579
-
MMBtu
$3,720
-
lb
TOTAL IMPLEMENTED $6,232 $1,675 $2,456
39,859
kWh
$56
-
kW-mo/yr
- $3,720
-
lb
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Solid Waste (non-haz) Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs