Assessment Year | 1992 |
---|---|
Principal Product | PLATED & FINISHED METALS |
NAICS |
n/a
|
SIC | 3471: Electroplating, Plating, Polishing, Anodizing, and Coloring |
Sales Range | $1 M to 5M |
# of Employees | 30 |
Plant Area |
n/a
|
Annual Production | 1,000,000
pieces
|
Production Hrs. Annual | 2,500
hrs
|
Location (State) | Michigan |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $43,190 | 529,308 |
kWh
|
$0.082 |
Natural Gas | $44,232 | 12,010 |
MMBtu
|
$3.68 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $4,129 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $226 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|
01 | 2.6221: Use most efficient equipment at it's maximum capacity and less efficient equipment only when necessary | $1,391 | - |
$1,391
16,999
kWh
|
- | |
02 | 2.3212: Optimize plant power factor | $1,387 | $1,966 |
$1,387
-
kWh
|
- | |
03 | 2.4133: Use most efficient type of electric motors | $226 | $2,240 |
$226
2,931
kWh
|
- | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $243 | $628 |
$359
4,396
kWh
|
$(-116.0) | |
05 | 2.4221: Install compressor air intakes in coolest locations | $882 | $200 |
$882
10,844
kWh
|
- | |
TOTAL RECOMMENDED | $4,129 | $5,034 |
$4,245
35,170
kWh
|
$(-116.0) | ||
TOTAL IMPLEMENTED | $226 | $2,240 |
$226
2,931
kWh
|
- |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs