Assessment Year | 2019 |
---|---|
Principal Product | Covered yarn |
NAICS | 313110: Fiber, Yarn, and Thread Mills |
SIC | 2281: Yarn Spinning Mills |
Sales Range | $5 M to 10M |
# of Employees | 60 |
Plant Area |
137,500
ft2
|
Annual Production | 780,000
lb
|
Production Hrs. Annual | 8,400
hrs
|
Location (State) | North Carolina |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $308,774 | 8,509,050 |
kWh
|
$0.036 |
Electricity Demand | $169,897 | 14,940 |
kW-mo/yr
|
$11.37 |
TOTAL YEARLY COSTS | $478,671 | |||
RECOMMENDED SAVINGS* | $31,941 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $25,714 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $9,633 | $59,736 |
$4,276
117,787
kWh
|
$5,357
-
kW-mo/yr
|
- | - | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,983 | $428 |
$1,972
54,302
kWh
|
$1,239
-
kW-mo/yr
|
$(-120.0) | $(-108.0) | |
03 | 2.4226: Use / purchase optimum sized compressor | $13,098 | $50,000 |
$10,096
278,134
kWh
|
$3,002
-
kW-mo/yr
|
- | - | |
04 | 2.7228: Avoid introducing hot, humid, or dirty air into hvac system | $2,107 | $3,000 |
$1,456
40,110
kWh
|
$651
-
kW-mo/yr
|
- | - | |
05 | 2.7241: Install outside air damper / economizer on hvac unit | $4,120 | $5,000 |
$4,120
113,493
kWh
|
- | - | - | |
TOTAL RECOMMENDED | $31,941 | $118,164 |
$21,920
603,826
kWh
|
$10,249
-
kW-mo/yr
|
$(-120.0) | $(-108.0) | ||
TOTAL IMPLEMENTED | $25,714 | $110,164 |
$16,344
450,223
kWh
|
$9,598
-
kW-mo/yr
|
$(-120.0) | $(-108.0) |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs