Assessment Year | 2017 |
---|---|
Principal Product | Jet engine parts |
NAICS | 336412: Aircraft Engine and Engine Parts Manufacturing |
SIC | 3724: Aircraft Engines and Engine Parts |
Sales Range | $50 M to 100M |
# of Employees | 350 |
Plant Area |
300,000
ft2
|
Annual Production | 3,000
pieces
|
Production Hrs. Annual | 7,200
hrs
|
Location (State) | Virginia |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,265,510 | 16,896,000 |
kWh
|
$0.075 |
Electricity Demand | $264,078 | 30,600 |
kW-mo/yr
|
$8.63 |
Natural Gas | $67,699 | 7,797 |
MMBtu
|
$8.68 |
TOTAL YEARLY COSTS | $1,597,287 | |||
RECOMMENDED SAVINGS* | $137,954 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $21,985 | $24,572 |
$16,419
219,207
kWh
|
$3,287
-
kW-mo/yr
|
$2,279 | |
02 | 2.4224: Upgrade controls on compressors | $74,459 | $160,000 |
$64,146
856,423
kWh
|
$10,313
-
kW-mo/yr
|
- | |
03 | 2.4221: Install compressor air intakes in coolest locations | $1,175 | $3,200 |
$787
10,513
kWh
|
$388
-
kW-mo/yr
|
- | |
04 | 2.2628: Utilize a less expensive cooling method | $5,207 | $14,400 |
$4,368
58,320
kWh
|
$839
-
kW-mo/yr
|
- | |
05 | 2.2628: Utilize a less expensive cooling method | $35,128 | $100,000 |
$29,660
396,000
kWh
|
$5,468
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $137,954 | $302,172 |
$115,380
1,540,463
kWh
|
$20,295
-
kW-mo/yr
|
$2,279 | ||
TOTAL IMPLEMENTED | - | - | - | - | - |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs