Assessment Year | 2017 |
---|---|
Principal Product | High speed packaging machines |
NAICS | 333993: Packaging Machinery Manufacturing |
SIC | 3565: Packaging Machinery |
Sales Range | $10 M to 50M |
# of Employees | 70 |
Plant Area |
87,000
ft2
|
Annual Production | 3
pieces
|
Production Hrs. Annual | 2,625
hrs
|
Location (State) | North Carolina |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $97,289 | 1,628,588 |
kWh
|
$0.060 | |
Electricity Demand | $20,117 | 4,859 |
kW-mo/yr
|
$4.14 | |
Natural Gas | $12,983 | 1,584 |
MMBtu
|
$8.20 | |
Waste Disposal Costs | |||||
Water Usage | $10,152 | 152 |
Tgal
|
$66.79 | |
Other Liquid (haz) | $448 | 448 |
gal
|
$1.00 | |
TOTAL YEARLY COSTS | $140,989 | ||||
RECOMMENDED SAVINGS* | $23,648 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $23,529 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Other Liquid (haz) Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $17,891 | $81,460 |
$13,744
230,219
kWh
|
$4,147
-
kW-mo/yr
|
- | - | |
02 | 2.7111: Reduce illumination to minimum necessary levels | $2,060 | $1,000 |
$1,568
26,271
kWh
|
$492
-
kW-mo/yr
|
- | - | |
03 | 2.7135: Install occupancy sensors | $941 | $1,500 |
$941
15,765
kWh
|
- | - | - | |
04 | 2.7134: Use photocell controls | $223 | $100 |
$223
3,739
kWh
|
- | - | - | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $428 | $100 |
$319
5,342
kWh
|
$109
-
kW-mo/yr
|
- | - | |
06 | 3.3125: Use distillation, evaporation to remove contaminants | $119 | $300 |
$(-78.0)
(-1,312)
kWh
|
$(-27.0)
-
kW-mo/yr
|
- |
$224
-
gal
|
|
07 | 2.7442: Keep doors and windows shut when not on use | $1,986 | $600 |
$174
2,917
kWh
|
- |
$1,812
-
MMBtu
|
- | |
TOTAL RECOMMENDED | $23,648 | $85,060 |
$16,891
282,941
kWh
|
$4,721
-
kW-mo/yr
|
$1,812
-
MMBtu
|
$224
-
gal
|
||
TOTAL IMPLEMENTED | $23,529 | $84,760 |
$16,969
284,253
kWh
|
$4,748
-
kW-mo/yr
|
$1,812
-
MMBtu
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Other Liquid (haz) Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs