Assessment Year | 2016 |
---|---|
Principal Product | Oligomers |
NAICS | 325199: All Other Basic Organic Chemical Manufacturing |
SIC | 2869: Industrial Organic Chemicals, Not Elsewhere Classified |
Sales Range | $50 M to 100M |
# of Employees | 50 |
Plant Area |
100,000
ft2
|
Annual Production | 30,000,000
lb
|
Production Hrs. Annual | 8,640
hrs
|
Location (State) | Virginia |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $315,686 | 10,369,658 |
kWh
|
$0.030 |
Electricity Demand | $271,599 | 18,465 |
kW-mo/yr
|
$14.71 |
Natural Gas | $525,759 | 106,064 |
MMBtu
|
$4.96 |
TOTAL YEARLY COSTS | $1,113,044 | |||
RECOMMENDED SAVINGS* | $113,347 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $23,545 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.2437: Recover waste heat from equipment | $68,453 | $280,000 | - | - |
$68,453
-
MMBtu
|
- | - | |
02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $19,493 | $48,500 |
$10,913
384,277
kWh
|
$8,580
-
kW-mo/yr
|
- | - | - | |
03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $4,986 | $18,150 |
$2,783
97,978
kWh
|
$2,203
-
kW-mo/yr
|
- | - | - | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,698 | $200 |
$1,373
48,341
kWh
|
$1,105
-
kW-mo/yr
|
- | $(-300.0) | $(-480.0) | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $14,208 | $33,756 |
$7,097
249,878
kWh
|
$5,711
-
kW-mo/yr
|
- | - | $1,400 | |
06 | 2.7134: Use photocell controls | $423 | $150 |
$423
14,890
kWh
|
- | - | - | - | |
07 | 2.4151: Develop a repair/replace policy | $2,230 | $4,256 |
$1,236
43,519
kWh
|
$994
-
kW-mo/yr
|
- | - | - | |
08 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,856 | $230 |
$1,029
36,222
kWh
|
$827
-
kW-mo/yr
|
- | - | - | |
TOTAL RECOMMENDED | $113,347 | $385,242 |
$24,854
875,105
kWh
|
$19,420
-
kW-mo/yr
|
$68,453
-
MMBtu
|
$(-300.0) | $920 | ||
TOTAL IMPLEMENTED | $23,545 | $56,512 |
$12,912
454,606
kWh
|
$10,013
-
kW-mo/yr
|
- | $(-300.0) | $920 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs