Assessment Year | 2015 |
---|---|
Principal Product | Aerosol valves |
NAICS | 326199: All Other Plastics Product Manufacturing |
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $100 M to 500M |
# of Employees | 250 |
Plant Area |
205,000
ft2
|
Annual Production | 900,000,000
pieces
|
Production Hrs. Annual | 7,200
hrs
|
Location (State) | South Carolina |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,033,626 | 24,610,680 |
kWh
|
$0.042 |
Electricity Demand | $502,902 | 46,663 |
kW-mo/yr
|
$10.78 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $114,014 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $110,554 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.8114: Change rate schedules or other changes in utility service | $63,028 | $500 |
$63,028
-
kWh
|
- | - | - | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $23,894 | $68,084 |
$11,979
285,226
kWh
|
$5,397
-
kW-mo/yr
|
- | $6,518 | |
03 | 2.7111: Reduce illumination to minimum necessary levels | $5,721 | $1,206 |
$3,551
84,546
kWh
|
$1,519
-
kW-mo/yr
|
- | $651 | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $542 | $160 |
$180
4,275
kWh
|
$63
-
kW-mo/yr
|
- | $299 | |
05 | 2.7135: Install occupancy sensors | $432 | $694 |
$432
10,296
kWh
|
- | - | - | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $363 | $1,170 |
$254
6,048
kWh
|
$109
-
kW-mo/yr
|
- | - | |
07 | 2.2511: Insulate bare equipment | $5,143 | $9,886 |
$5,143
122,472
kWh
|
- | - | - | |
08 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $10,396 | $200 |
$8,121
193,363
kWh
|
$3,475
-
kW-mo/yr
|
$(-720.0) | $(-480.0) | |
09 | 2.4239: Eliminate or reduce compressed air usage | $971 | $2,000 |
$680
16,189
kWh
|
$291
-
kW-mo/yr
|
- | - | |
10 | 2.4231: Reduce the pressure of compressed air to the minimum required | $314 | $100 |
$220
5,244
kWh
|
$94
-
kW-mo/yr
|
- | - | |
11 | 2.3132: Recharge batteries on during off-peak demand periods | $1,035 | $200 |
$801
-
kWh
|
$234
-
kW-mo/yr
|
- | - | |
12 | 2.4151: Develop a repair/replace policy | $2,175 | $4,256 |
$1,523
36,266
kWh
|
$652
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $114,014 | $88,456 |
$95,912
763,925
kWh
|
$11,834
-
kW-mo/yr
|
$(-720.0) | $6,988 | ||
TOTAL IMPLEMENTED | $110,554 | $82,100 |
$93,489
706,226
kWh
|
$10,797
-
kW-mo/yr
|
$(-720.0) | $6,988 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs