Assessment Year | 2015 |
---|---|
Principal Product | Truck bodies |
NAICS | 336211: Motor Vehicle Body Manufacturing |
SIC | 3713: Truck and Bus Bodies |
Sales Range | $10 M to 50M |
# of Employees | 156 |
Plant Area |
250,000
ft2
|
Annual Production | 450
pieces
|
Production Hrs. Annual | 2,250
hrs
|
Location (State) | North Carolina |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $136,763 | 1,295,540 |
kWh
|
$0.11 |
Electricity Demand | $41,486 | 5,456 |
kW-mo/yr
|
$7.60 |
Natural Gas | $57,335 | 7,277 |
MMBtu
|
$7.88 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $55,261 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $20,391 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $18,953 | $23,900 |
$9,315
124,209
kWh
|
$9,638
-
kW-mo/yr
|
- | - | - | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $634 | $100 |
$449
5,992
kWh
|
$465
-
kW-mo/yr
|
- | $(-100.0) | $(-180.0) | |
03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,820 | $100 |
$894
11,925
kWh
|
$926
-
kW-mo/yr
|
- | - | - | |
04 | 2.2437: Recover waste heat from equipment | $2,519 | $2,100 | - | - |
$2,519
-
MMBtu
|
- | - | |
05 | 2.4239: Eliminate or reduce compressed air usage | $3,444 | $2,700 |
$703
12,657
kWh
|
$2,741
-
kW-mo/yr
|
- | - | - | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,015 | $984 |
$1,404
12,562
kWh
|
$383
-
kW-mo/yr
|
- | - | $228 | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $17,742 | $46,719 |
$13,943
120,825
kWh
|
$3,574
-
kW-mo/yr
|
- | - | $225 | |
08 | 2.7134: Use photocell controls | $382 | $150 |
$382
5,100
kWh
|
- | - | - | - | |
09 | 2.7135: Install occupancy sensors | $316 | $868 |
$316
2,542
kWh
|
- | - | - | - | |
10 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,426 | $4,394 |
$1,426
9,198
kWh
|
- | - | - | - | |
11 | 2.4322: Use or replace with energy efficient substitutes | $3,900 | $18,900 |
$3,900
47,544
kWh
|
- | - | - | - | |
12 | 2.7224: Reduce space conditioning during non-working hours | $381 | $525 |
$381
2,460
kWh
|
- | - | - | - | |
13 | 2.4151: Develop a repair/replace policy | $1,729 | $4,256 |
$850
11,333
kWh
|
$879
-
kW-mo/yr
|
- | - | - | |
TOTAL RECOMMENDED | $55,261 | $105,696 |
$33,963
366,347
kWh
|
$18,606
-
kW-mo/yr
|
$2,519
-
MMBtu
|
$(-100.0) | $273 | ||
TOTAL IMPLEMENTED | $20,391 | $47,803 |
$15,796
139,379
kWh
|
$4,422
-
kW-mo/yr
|
- | $(-100.0) | $273 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs