Assessment Year | 2014 |
---|---|
Principal Product | Manufactured Homes |
NAICS | 321991: Manufactured Home (Mobile Home) Manufacturing |
SIC | 2451: Mobile Homes |
Sales Range | $10 M to 50M |
# of Employees | 101 |
Plant Area |
95,000
ft2
|
Annual Production | 200
pieces
|
Production Hrs. Annual | 2,125
hrs
|
Location (State) | Virginia |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $66,592 | 782,500 |
kWh
|
$0.085 |
Electricity Demand | $11,214 | 3,115 |
kW-mo/yr
|
$3.60 |
Electricity Fees | $4,411 | - |
|
- |
LPG | $52,534 | 1,917 |
MMBtu
|
$27.40 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $23,503 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $20,222 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | LPG Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7312: Minimize use of outside make-up air for ventilation except when used for economizer cycle | $9,684 | $2,200 | - | - |
$9,684
-
MMBtu
|
- | - | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $865 | $100 |
$1,134
13,324
kWh
|
$271
-
kW-mo/yr
|
- | $(-300.0) | $(-240.0) | |
03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,274 | $1,950 |
$1,028
12,084
kWh
|
$246
-
kW-mo/yr
|
- | - | - | |
04 | 2.2437: Recover waste heat from equipment | $1,952 | $2,300 | - | - |
$1,952
-
MMBtu
|
- | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,695 | $28,977 |
$5,469
64,262
kWh
|
$1,303
-
kW-mo/yr
|
- | - | $(-77.0) | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $520 | $4,006 |
$423
4,976
kWh
|
$97
-
kW-mo/yr
|
- | - | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,026 | $240 |
$546
5,413
kWh
|
$31
-
kW-mo/yr
|
- | - | $449 | |
08 | 2.7135: Install occupancy sensors | $359 | $574 |
$359
4,219
kWh
|
- | - | - | - | |
09 | 2.4151: Develop a repair/replace policy | $1,128 | $4,256 |
$911
10,703
kWh
|
$217
-
kW-mo/yr
|
- | - | - | |
TOTAL RECOMMENDED | $23,503 | $44,603 |
$9,870
114,981
kWh
|
$2,165
-
kW-mo/yr
|
$11,636
-
MMBtu
|
$(-300.0) | $132 | ||
TOTAL IMPLEMENTED | $20,222 | $33,817 |
$7,149
82,999
kWh
|
$1,605
-
kW-mo/yr
|
$11,636
-
MMBtu
|
$(-300.0) | $132 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | LPG Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs