ITAC Assessment: NC0508
ITAC logo
ITAC Assessment: NC0508
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 2014
Principal Product Manufactured Homes
NAICS 321991: Manufactured Home (Mobile Home) Manufacturing
SIC 2451: Mobile Homes
Sales Range $10
M
to 50
M
# of Employees 101
Plant Area 95,000
ft2
Annual Production 200
pieces
Production Hrs. Annual 2,125
hrs
Location (State) Virginia

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $66,592 782,500
kWh
Electricity Demand $11,214 3,115
kW-mo/yr
Electricity Fees $4,411 -
LPG $52,534 1,917
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $23,503 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $20,222

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings LPG Savings Personnel Changes Savings Ancillary Material Cost Savings
01 2.7312: Minimize use of outside make-up air for ventilation except when used for economizer cycle $9,684 $2,200 - - $9,684
-
MMBtu
- -
02 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $865 $100 $1,134
13,324
kWh
$271
-
kW-mo/yr
- $(-300.0) $(-240.0)
03 2.4231: Reduce the pressure of compressed air to the minimum required $1,274 $1,950 $1,028
12,084
kWh
$246
-
kW-mo/yr
- - -
04 2.2437: Recover waste heat from equipment $1,952 $2,300 - - $1,952
-
MMBtu
- -
05 2.7142: Utilize higher efficiency lamps and/or ballasts $6,695 $28,977 $5,469
64,262
kWh
$1,303
-
kW-mo/yr
- - $(-77.0)
06 2.7142: Utilize higher efficiency lamps and/or ballasts $520 $4,006 $423
4,976
kWh
$97
-
kW-mo/yr
- - -
07 2.7142: Utilize higher efficiency lamps and/or ballasts $1,026 $240 $546
5,413
kWh
$31
-
kW-mo/yr
- - $449
08 2.7135: Install occupancy sensors $359 $574 $359
4,219
kWh
- - - -
09 2.4151: Develop a repair/replace policy $1,128 $4,256 $911
10,703
kWh
$217
-
kW-mo/yr
- - -
TOTAL RECOMMENDED $23,503 $44,603 $9,870
114,981
kWh
$2,165
-
kW-mo/yr
$11,636
-
MMBtu
$(-300.0) $132
TOTAL IMPLEMENTED $20,222 $33,817 $7,149
82,999
kWh
$1,605
-
kW-mo/yr
$11,636
-
MMBtu
$(-300.0) $132
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings LPG Savings Personnel Changes Savings Ancillary Material Cost Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs