Assessment Year | 2013 |
---|---|
Principal Product | Plastic food containers |
NAICS | 326199: All Other Plastics Product Manufacturing |
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $50 M to 100M |
# of Employees | 500 |
Plant Area |
315,000
ft2
|
Annual Production | 1,000,000,000
pieces
|
Production Hrs. Annual | 8,400
hrs
|
Location (State) | Virginia |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $2,024,874 | 33,003,250 |
kWh
|
$0.061 |
Electricity Demand | $680,114 | 56,050 |
kW-mo/yr
|
$12.13 |
Natural Gas | $42,173 | 5,100 |
MMBtu
|
$8.27 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $144,441 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $65,995 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Water Disposal Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $68,635 | $375 |
$53,529
871,802
kWh
|
$15,106
-
kW-mo/yr
|
- | - | - | |
02 | 2.4224: Upgrade controls on compressors | $35,397 | $25,000 |
$35,397
576,508
kWh
|
- | - | - | - | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $4,920 | $100 |
$5,387
87,730
kWh
|
$1,513
-
kW-mo/yr
|
- | $(-1,500.0) | $(-480.0) | |
04 | 2.4322: Use or replace with energy efficient substitutes | $21,685 | $33,000 |
$16,406
267,200
kWh
|
$5,279
-
kW-mo/yr
|
- | - | - | |
05 | 2.7135: Install occupancy sensors | $7,375 | $4,511 |
$7,375
120,120
kWh
|
- | - | - | - | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $667 | $1,630 |
$520
8,467
kWh
|
$147
-
kW-mo/yr
|
- | - | - | |
07 | 3.4155: Meter waste water | $3,326 | $4,200 | - | - |
$3,326
-
Tgal
|
- | - | |
08 | 2.7241: Install outside air damper / economizer on hvac unit | $1,569 | $4,000 |
$1,569
25,558
kWh
|
- | - | - | - | |
09 | 2.2511: Insulate bare equipment | $867 | $660 |
$792
12,904
kWh
|
$75
-
kW-mo/yr
|
- | - | - | |
TOTAL RECOMMENDED | $144,441 | $73,476 |
$120,975
1,970,289
kWh
|
$22,120
-
kW-mo/yr
|
$3,326
-
Tgal
|
$(-1,500.0) | $(-480.0) | ||
TOTAL IMPLEMENTED | $65,995 | $63,930 |
$57,710
939,905
kWh
|
$6,939
-
kW-mo/yr
|
$3,326
-
Tgal
|
$(-1,500.0) | $(-480.0) | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Water Disposal Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs