Assessment Year | 2011 |
---|---|
Principal Product | Elecrical wiring devices |
NAICS | 335931: Current-Carrying Wiring Device Manufacturing |
SIC | 3643: Current-Carrying Wiring Devices |
Sales Range | $100 M to 500M |
# of Employees | 70 |
Plant Area |
330,000
ft2
|
Annual Production | 25,000
pieces
|
Production Hrs. Annual | 4,250
hrs
|
Location (State) | South Carolina |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $225,941 | 3,732,900 |
kWh
|
$0.061 |
Electricity Demand | $29,029 | 8,923 |
kW-mo/yr
|
$3.25 |
Electricity Fees | $7,880 | - |
|
- |
Natural Gas | $13,320 | 1,198 |
MMBtu
|
$11.12 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $71,084 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $47,322 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
---|---|---|---|---|---|---|---|
01 | 2.8114: Change rate schedules or other changes in utility service | $23,638 | - |
$19,836
-
kWh
|
- | $3,802 | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $44,479 | $72,211 |
$39,150
646,786
kWh
|
$5,329
-
kW-mo/yr
|
- | |
03 | 2.7144: Install spectral reflectors / delamp | $1,887 | $7,760 |
$1,453
24,008
kWh
|
$434
-
kW-mo/yr
|
- | |
04 | 2.7135: Install occupancy sensors | $661 | $1,911 |
$661
10,915
kWh
|
- | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $124 | $31 |
$96
1,580
kWh
|
$28
-
kW-mo/yr
|
- | |
06 | 2.7261: Install timers and/or thermostats | $295 | $1,500 |
$295
4,885
kWh
|
- | - | |
TOTAL RECOMMENDED | $71,084 | $83,413 |
$61,491
688,174
kWh
|
$5,791
-
kW-mo/yr
|
$3,802 | ||
TOTAL IMPLEMENTED | $47,322 | $83,382 |
$41,559
686,594
kWh
|
$5,763
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs