Assessment Year | 2007 |
---|---|
Principal Product | Gasoline dispensers |
NAICS | 333913: Measuring and Dispensing Pump Manufacturing |
SIC | 3586: Measuring and Dispensing Pumps |
Sales Range | $100 M to 500M |
# of Employees | 1,100 |
Plant Area |
850,000
ft2
|
Annual Production | 25,000
pieces
|
Production Hrs. Annual | 4,000
hrs
|
Location (State) | North Carolina |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $661,462 | 21,345,000 |
kWh
|
$0.031 |
Electricity Demand | $414,395 | 45,360 |
kW-mo/yr
|
$9.14 |
Electricity Fees | $32,722 | - |
|
- |
Natural Gas | $704,304 | 69,181 |
MMBtu
|
$10.18 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $44,034 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $21,765 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.2514: Cover open tanks | $11,745 | $2,500 |
$11,745
379,000
kWh
|
- | - | - | - | |
02 | 2.2437: Recover waste heat from equipment | $9,750 | $13,500 | - | - |
$9,750
-
MMBtu
|
- | - | |
03 | 2.6218: Turn off equipment when not in use | $5,420 | $1,500 |
$5,420
175,000
kWh
|
- | - | - | - | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,910 | $100 |
$1,909
61,586
kWh
|
$701
-
kW-mo/yr
|
- | $(-300.0) | $(-400.0) | |
05 | 2.1232: Keep boiler tubes clean | $2,955 | $1,000 | - | - |
$2,955
-
MMBtu
|
- | - | |
06 | 2.7241: Install outside air damper / economizer on hvac unit | $1,730 | - |
$3,730
120,300
kWh
|
- | - | - | $(-2,000.0) | |
07 | 2.4151: Develop a repair/replace policy | $968 | $2,159 |
$537
17,317
kWh
|
$431
-
kW-mo/yr
|
- | - | - | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $8,862 | - |
$4,909
158,400
kWh
|
$3,953
-
kW-mo/yr
|
- | - | - | |
09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $694 | $1,564 |
$397
11,849
kWh
|
$297
-
kW-mo/yr
|
- | - | - | |
TOTAL RECOMMENDED | $44,034 | $22,323 |
$28,647
923,452
kWh
|
$5,382
-
kW-mo/yr
|
$12,705
-
MMBtu
|
$(-300.0) | $(-2,400.0) | ||
TOTAL IMPLEMENTED | $21,765 | $16,100 |
$11,059
356,886
kWh
|
$701
-
kW-mo/yr
|
$12,705
-
MMBtu
|
$(-300.0) | $(-2,400.0) | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs