Assessment Year | 2006 |
---|---|
Principal Product | Cases of Cigars |
NAICS | 312230: Tobacco Manufacturing |
SIC | 2120: |
Sales Range | $1 M to 5M |
# of Employees | 45 |
Plant Area |
55,000
ft2
|
Annual Production | 84,000
pieces
|
Production Hrs. Annual | 2,000
hrs
|
Location (State) | North Carolina |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $51,027 | 1,163,600 |
kWh
|
$0.044 |
Electricity Demand | $56,745 | 5,053 |
kW-mo/yr
|
$11.23 |
Natural Gas | $17,850 | 1,183 |
MMBtu
|
$15.09 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $9,844 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $2,677 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.2437: Recover waste heat from equipment | $2,660 | $9,688 | - | - |
$2,660
-
MMBtu
|
- | - | |
02 | 2.7313: Recycle air for heating, ventilation and air conditioning | $1,147 | $2,800 | - | - |
$1,147
-
MMBtu
|
- | - | |
03 | 2.2437: Recover waste heat from equipment | $2,475 | $4,243 | - | - |
$2,475
-
MMBtu
|
- | - | |
04 | 2.6231: Utilize controls to operate equipment only when needed | $885 | $1,000 |
$885
17,530
kWh
|
- | - | - | - | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $484 | $100 |
$465
9,200
kWh
|
$619
-
kW-mo/yr
|
- | $(-300.0) | $(-300.0) | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,135 | $1,000 |
$913
18,094
kWh
|
$1,222
-
kW-mo/yr
|
- | - | - | |
07 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $58 | $39 |
$19
387
kWh
|
$39
-
kW-mo/yr
|
- | - | - | |
TOTAL RECOMMENDED | $9,844 | $18,870 |
$2,282
45,211
kWh
|
$1,880
-
kW-mo/yr
|
$6,282
-
MMBtu
|
$(-300.0) | $(-300.0) | ||
TOTAL IMPLEMENTED | $2,677 | $1,139 |
$1,397
27,681
kWh
|
$1,880
-
kW-mo/yr
|
- | $(-300.0) | $(-300.0) | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs