Assessment Year 2005
Principal Product Electronic data storage units
NAICS 334419: Other Electronic Component Manufacturing
SIC 3670:
Sales Range $100
M
to 500
M
# of Employees 340
Plant Area 338,000
ft2
Annual Production 100,000
pieces
Production Hrs. Annual 6,000
hrs
Location (State) North Carolina

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $630,281 18,188,925
kWh
Electricity Demand $285,871 33,921
kW-mo/yr
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $185,573 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $118,032

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Ancillary Material Cost Savings
01 2.2437: Recover waste heat from equipment $2,020 $3,726 $1,378
39,734
kWh
$642
-
kW-mo/yr
-
02 2.7142: Utilize higher efficiency lamps and/or ballasts $26,893 $50 $17,022
490,560
kWh
$5,611
-
kW-mo/yr
$4,260
03 2.7142: Utilize higher efficiency lamps and/or ballasts $87,704 $291,200 $65,962
1,900,920
kWh
$21,742
-
kW-mo/yr
-
04 2.7229: Air condition only space necessary $8,095 - $5,653
162,908
kWh
$2,442
-
kW-mo/yr
-
05 2.7124: Make a practice of turning off lights when not needed $30,533 - $30,533
983,040
kWh
- -
06 2.7261: Install timers and/or thermostats $16,545 $10,648 $16,545
532,703
kWh
- -
07 2.7221: Lower temperature during the winter season and vice-versa $13,783 $150 $11,544
332,693
kWh
$2,239
-
kW-mo/yr
-
TOTAL RECOMMENDED $185,573 $305,774 $148,637
4,442,558
kWh
$32,676
-
kW-mo/yr
$4,260
TOTAL IMPLEMENTED $118,032 $301,998 $94,051
2,766,316
kWh
$23,981
-
kW-mo/yr
-
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Ancillary Material Cost Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs