Assessment Year | 2003 |
---|---|
Principal Product | Polyurethane foam |
NAICS |
n/a
|
SIC | 3086: Plastics Foam Products |
Sales Range | $10 M to 50M |
# of Employees | 190 |
Plant Area |
500,000
ft2
|
Annual Production | 30,000,000
lb
|
Production Hrs. Annual | 6,000
hrs
|
Location (State) | North Carolina |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $268,045 | 10,148,000 |
kWh
|
$0.026 |
Electricity Demand | $132,423 | 18,906 |
kW-mo/yr
|
$7.00 |
Electricity Fees | $8,606 | - |
|
- |
Natural Gas | $113,717 | 18,434 |
MMBtu
|
$6.17 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $90,953 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7111: Reduce illumination to minimum necessary levels | $81,956 | $105,000 | n/a |
$50,803
1,881,600
kWh
|
$25,320
-
kW-mo/yr
|
- | $5,833 |
02 | 2.1133: Adjust burners for efficient operation | $3,127 | $1,000 | - | - |
$3,127
-
MMBtu
|
- | |
03 | 2.4154: Avoid rewinding motors more than twice | $694 | $432 |
$423
15,672
kWh
|
$271
-
kW-mo/yr
|
- | - | |
04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $130 | $48 |
$42
1,551
kWh
|
$88
-
kW-mo/yr
|
- | - | |
05 | 2.3113: Make ice during off peak hours for cooling | $5,046 | $2,000 |
$688
(-10,767)
kWh
|
$4,358
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $90,953 | $108,480 |
$51,956
1,888,056
kWh
|
$30,037
-
kW-mo/yr
|
$3,127
-
MMBtu
|
$5,833 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs