Assessment Year | 2002 |
---|---|
Principal Product | Lockers, shelving, and racks |
NAICS |
n/a
|
SIC | 3499: Fabricated Metal Products, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 240 |
Plant Area |
483,000
ft2
|
Annual Production | 33,000,000
lb
|
Production Hrs. Annual | 4,000
hrs
|
Location (State) | North Carolina |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $135,908 | 5,533,486 |
kWh
|
$0.025 |
Electricity Demand | $186,471 | 12,693 |
kW-mo/yr
|
$14.69 |
Electricity Fees | $38,225 | - |
|
- |
Natural Gas | $290,782 | 49,616 |
MMBtu
|
$5.86 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $155,689 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $1,251 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings | Increase in Production Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.3113: Make ice during off peak hours for cooling | $13,524 | $16,000 | n/a |
$(-374.0)
(-30,511)
kWh
|
$13,898
-
kW-mo/yr
|
- | - | - |
02 | 2.1113: Reduce combustion air flow to optimum | $37,000 | $12,000 | n/a | - | - |
$37,000
-
MMBtu
|
- | - |
03 | 2.2437: Recover waste heat from equipment | $11,259 | $20,000 |
$(-583.0)
(-24,513)
kWh
|
$(-1,044.0)
-
kW-mo/yr
|
$12,886
-
MMBtu
|
- | - | |
04 | 2.2437: Recover waste heat from equipment | $12,244 | $12,245 |
$(-391.0)
(-16,432)
kWh
|
$(-702.0)
-
kW-mo/yr
|
$13,337
-
MMBtu
|
- | - | |
05 | 2.7229: Air condition only space necessary | $65,851 | $10,750 |
$922
38,737
kWh
|
$5,929
-
kW-mo/yr
|
- | $59,000 | - | |
06 | 4.651: Install back-up equipment | $13,440 | $35,000 | - | - | - | - | $13,440 | |
07 | 2.4151: Develop a repair/replace policy | $798 | $1,293 |
$285
11,961
kWh
|
$513
-
kW-mo/yr
|
- | - | - | |
08 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $322 | $921 |
$146
6,153
kWh
|
$176
-
kW-mo/yr
|
- | - | - | |
09 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,251 | $420 |
$447
18,786
kWh
|
$804
-
kW-mo/yr
|
- | - | - | |
TOTAL RECOMMENDED | $155,689 | $108,629 |
$452
4,181
kWh
|
$19,574
-
kW-mo/yr
|
$63,223
-
MMBtu
|
$59,000 | $13,440 | ||
TOTAL IMPLEMENTED | $1,251 | $420 |
$447
18,786
kWh
|
$804
-
kW-mo/yr
|
- | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings | Increase in Production Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs