Assessment Year 2002
Principal Product Corrugated board
NAICS
n/a
SIC 2653: Corrugated and Solid Fiber Boxes
Sales Range $10
M
to 50
M
# of Employees 118
Plant Area 250,000
ft2
Annual Production 7,000,000
pieces
Production Hrs. Annual 6,000
hrs
Location (State) North Carolina

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $169,207 3,967,920
kWh
Electricity Demand $53,684 10,424
kW-mo/yr
Electricity Fees $29 -
Natural Gas $140,320 25,601
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $39,989 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $26,415

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings Natural Gas Savings
01 2.8114: Change rate schedules or other changes in utility service $7,487 $1,000 - $(-37,487.0)
-
kW-mo/yr
$44,974 -
02 2.3131: Reschedule plant operations or reduce load to avoid peaks $6,087 - $3,534
82,600
kWh
$2,553
-
kW-mo/yr
- -
03 2.7313: Recycle air for heating, ventilation and air conditioning $8,379 $7,882 - - - $8,379
-
MMBtu
04 2.4151: Develop a repair/replace policy $2,115 $1,075 $1,698
39,673
kWh
$417
-
kW-mo/yr
- -
05 2.7241: Install outside air damper / economizer on hvac unit $14,743 $40,000 $14,743
344,536
kWh
- - -
06 2.2511: Insulate bare equipment $982 $1,936 - - - $982
-
MMBtu
07 2.7142: Utilize higher efficiency lamps and/or ballasts $196 $334 $158
3,703
kWh
$38
-
kW-mo/yr
- -
TOTAL RECOMMENDED $39,989 $52,227 $20,133
470,512
kWh
$(-34,479.0)
-
kW-mo/yr
$44,974 $9,361
-
MMBtu
TOTAL IMPLEMENTED $26,415 $51,227 $16,599
387,912
kWh
$455
-
kW-mo/yr
- $9,361
-
MMBtu
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings Natural Gas Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs