Assessment Year 2002
Principal Product Frames
NAICS
n/a
SIC 2426: Hardwood Dimension and Flooring Mills
Sales Range $5
M
to 10
M
# of Employees 70
Plant Area 90,000
ft2
Annual Production 10,000
thousand feet
Production Hrs. Annual 4,000
hrs
Location (State) North Carolina

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $91,729 1,498,800
kWh
Electricity Demand $30,909 4,755
kW-mo/yr
Electricity Fees $4,111 -
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $63,232 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $52,630

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Administrative Changes Savings
01 2.3192: Use fossil fuel powered generator during peak demand periods $44,473 $120,000 - $16,068
-
kW-mo/yr
$28,405
02 2.7145: Install skylights $1,646 $540 $1,646
26,980
kWh
- -
03 2.7111: Reduce illumination to minimum necessary levels $2,600 $2,665 $2,070
33,942
kWh
$530
-
kW-mo/yr
-
04 2.7142: Utilize higher efficiency lamps and/or ballasts $591 $1,597 $364
5,966
kWh
$227
-
kW-mo/yr
-
05 2.4323: Use optimum size and capacity equipment $10,011 $7,795 $10,011
164,120
kWh
- -
06 2.4231: Reduce the pressure of compressed air to the minimum required $427 $100 $324
5,304
kWh
$103
-
kW-mo/yr
-
07 2.4151: Develop a repair/replace policy $774 $863 $563
9,233
kWh
$211
-
kW-mo/yr
-
08 2.4111: Utilize energy-efficient belts and other improved mechanisms $1,850 $1,004 $1,402
22,982
kWh
$448
-
kW-mo/yr
-
09 2.6218: Turn off equipment when not in use $860 $500 $860
14,093
kWh
- -
TOTAL RECOMMENDED $63,232 $135,064 $17,240
282,620
kWh
$17,587
-
kW-mo/yr
$28,405
TOTAL IMPLEMENTED $52,630 $125,672 $6,865
112,534
kWh
$17,360
-
kW-mo/yr
$28,405
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Administrative Changes Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs