| Assessment Year | 2002 |
|---|---|
| Principal Product | Forged and cast metal parts |
| NAICS |
n/a
|
| SIC | 3312: Steel Works, Blast Furnaces (Including Coke Ovens), and Rolling Mills |
| Sales Range | $50 M to 100M |
| # of Employees | 200 |
| Plant Area |
280,000
ft2
|
| Annual Production | 17,662,000
lb
|
| Production Hrs. Annual | 6,000
hrs
|
| Location (State) | North Carolina |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $884,264 | 26,894,911 |
kWh
|
$0.033 |
| Electricity Demand | $309,804 | 14,865 |
kW-mo/yr
|
$20.84 |
| Electricity Fees | $49,740 | - |
|
- |
| Natural Gas | $745,180 | 92,623 |
MMBtu
|
$8.05 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $13,715 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $11,706 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.7313: Recycle air for heating, ventilation and air conditioning | $6,456 | $8,000 | - | - |
$6,456
-
MMBtu
|
|
| 02 | 2.7241: Install outside air damper / economizer on hvac unit | $1,506 | $6,000 |
$1,506
45,770
kWh
|
- | - | |
| 03 | 2.4151: Develop a repair/replace policy | $4,751 | $6,493 |
$2,354
71,541
kWh
|
$2,397
-
kW-mo/yr
|
- | |
| 04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $503 | $576 |
$249
7,569
kWh
|
$254
-
kW-mo/yr
|
- | |
| 05 | 2.1232: Keep boiler tubes clean | $499 | $1,600 |
$499
62
kWh
|
- | - | |
| TOTAL RECOMMENDED | $13,715 | $22,669 |
$4,608
124,942
kWh
|
$2,651
-
kW-mo/yr
|
$6,456
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $11,706 | $16,093 |
$2,853
71,603
kWh
|
$2,397
-
kW-mo/yr
|
$6,456
-
MMBtu
|
||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs