Assessment Year | 2001 |
---|---|
Principal Product | Knitted fabric |
NAICS |
n/a
|
SIC | 2253: Knit Outerwear Mills |
Sales Range | $10 M to 50M |
# of Employees | 125 |
Plant Area |
125,804
ft2
|
Annual Production | 13,500,000
lb
|
Production Hrs. Annual | 8,488
hrs
|
Location (State) | North Carolina |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $104,499 | 3,628,440 |
kWh
|
$0.029 |
Electricity Demand | $79,397 | 9,284 |
kW-mo/yr
|
$8.55 |
LPG | $7,772 | 914 |
MMBtu
|
$8.50 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $11,249 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $4,568 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Solid Waste (non-haz) Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7243: Improve air circulation with destratification fans / other methods | $2,845 | $5,600 |
$1,282
44,525
kWh
|
$(-137.0)
-
kW-mo/yr
|
$1,700
-
MMBtu
|
- | - | |
02 | 2.4224: Upgrade controls on compressors | $2,519 | $5,600 |
$2,519
87,480
kWh
|
- | - | - | - | |
03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $3,161 | $5,700 |
$2,131
74,003
kWh
|
$1,030
-
kW-mo/yr
|
- | - | - | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $163 | $200 |
$111
3,851
kWh
|
$52
-
kW-mo/yr
|
- | - | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,886 | $2,360 |
$335
11,644
kWh
|
$163
-
kW-mo/yr
|
- | - | $1,388 | |
06 | 3.5316: Contract a wood pallet recycling company | $675 | $200 | - | - | - |
$675
-
lb
|
- | |
TOTAL RECOMMENDED | $11,249 | $19,660 |
$6,378
221,503
kWh
|
$1,108
-
kW-mo/yr
|
$1,700
-
MMBtu
|
$675
-
lb
|
$1,388 | ||
TOTAL IMPLEMENTED | $4,568 | $8,160 |
$2,965
102,975
kWh
|
$215
-
kW-mo/yr
|
- | - | $1,388 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Solid Waste (non-haz) Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs