Assessment Year | 2023 |
---|---|
Principal Product | Hydraulic Oil Filters and Components |
NAICS | 333999: All Other Miscellaneous General Purpose Machinery Manufacturing |
SIC | 3569: General Industrial Machinery and Equipment, Not Elsewhere |
Sales Range | $50 M to 100M |
# of Employees | 130 |
Plant Area |
115,000
ft2
|
Annual Production | 1,500,000
units
|
Production Hrs. Annual | 6,552
hrs
|
Location (State) | Ohio |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $201,007 | 2,340,147 |
kWh
|
$0.086 |
Electricity Demand | $101,278 | 5,985 |
kW-mo/yr
|
$16.92 |
Electricity Fees | $(-8,940.5) | - |
|
- |
Natural Gas | $23,139 | 2,694 |
MMBtu
|
$8.59 |
TOTAL YEARLY COSTS | $316,483 | |||
RECOMMENDED SAVINGS* | $8,110 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $4,749 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,186 | - |
$1,186
13,789
kWh
|
- | - | |
02 | 2.6218: Turn off equipment when not in use | $2,322 | - |
$2,322
27,003
kWh
|
- | - | |
03 | 2.7111: Reduce illumination to minimum necessary levels | $1,919 | - |
$1,841
21,406
kWh
|
$78
-
kW-mo/yr
|
- | |
04 | 2.7134: Use photocell controls | $138 | $348 |
$138
1,606
kWh
|
- | - | |
05 | 2.7135: Install occupancy sensors | $863 | $112 |
$863
10,031
kWh
|
- | - | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $643 | $1,100 |
$643
7,477
kWh
|
- | - | |
07 | 2.7447: Install vinyl strip / high speed / air curtain doors | $550 | $776 |
$550
6,396
kWh
|
- | - | |
08 | 2.7492: Use proper thickness of insulation on building envelope | $490 | $1,162 | - | - |
$490
-
MMBtu
|
|
TOTAL RECOMMENDED | $8,110 | $3,498 |
$7,543
87,708
kWh
|
$78
-
kW-mo/yr
|
$490
-
MMBtu
|
||
TOTAL IMPLEMENTED | $4,749 | $1,560 |
$4,671
54,309
kWh
|
$78
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs