| Assessment Year | 2000 |
|---|---|
| Principal Product | Plastic bottles |
| NAICS |
n/a
|
| SIC | 3085: Plastics Bottles |
| Sales Range | $10 M to 50M |
| # of Employees | 100 |
| Plant Area |
160,000
ft2
|
| Annual Production | 400,000,000
pieces
|
| Production Hrs. Annual | 8,760
hrs
|
| Location (State) | North Carolina |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $418,804 | 16,614,596 |
kWh
|
$0.025 |
| Electricity Demand | $274,478 | 29,060 |
kW-mo/yr
|
$9.45 |
| Electricity Fees | $23,191 | - |
|
- |
| Natural Gas | $8,969 | 1,388 |
MMBtu
|
$6.46 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $129,989 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $3,831 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $762 | $3,710 |
$373
14,654
kWh
|
$389
-
kW-mo/yr
|
- | - | |
| 02 | 2.4151: Develop a repair/replace policy | $3,831 | $3,617 |
$2,537
100,821
kWh
|
$1,294
-
kW-mo/yr
|
- | - | |
| 03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,422 | $56 |
$941
37,222
kWh
|
$481
-
kW-mo/yr
|
- | - | |
| 04 | 2.7111: Reduce illumination to minimum necessary levels | $1,211 | $3,850 |
$430
16,999
kWh
|
$781
-
kW-mo/yr
|
- | - | |
| 05 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $35,491 | $500 |
$6,893
214,537
kWh
|
$11,078
-
kW-mo/yr
|
$17,520 | - | |
| 06 | 2.7228: Avoid introducing hot, humid, or dirty air into hvac system | $64,272 | $64,142 |
$42,506
1,687,280
kWh
|
$21,766
-
kW-mo/yr
|
- | - | |
| 07 | 4.322: Eliminate old stock and modify inventory control | $23,000 | $1,000 | - | - | $15,000 | $8,000 | |
| TOTAL RECOMMENDED | $129,989 | $76,875 |
$53,680
2,071,513
kWh
|
$35,789
-
kW-mo/yr
|
$32,520 | $8,000 | ||
| TOTAL IMPLEMENTED | $3,831 | $3,617 |
$2,537
100,821
kWh
|
$1,294
-
kW-mo/yr
|
- | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Administrative Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs