Assessment Year | 1994 |
---|---|
Principal Product | Ladies Hosiery |
NAICS |
n/a
|
SIC | 2251: Women's Full-Length and Knee-Length Hosiery, Except Socks |
Sales Range | $10 M to 50M |
# of Employees | 170 |
Plant Area |
90,000
ft2
|
Annual Production | 0
units
|
Production Hrs. Annual | 4,000
hrs
|
Location (State) | North Carolina |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $115,546 | 1,858,441 |
kWh
|
$0.062 |
Natural Gas | $114,783 | 31,451 |
MMBtu
|
$3.65 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $32,070 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $10,423 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,151 | $1,502 |
$2,151
35,756
kWh
|
- | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $8,024 | $13,329 |
$8,024
168,523
kWh
|
- | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $248 | $120 |
$248
4,103
kWh
|
- | |
04 | 2.4221: Install compressor air intakes in coolest locations | $198 | $310 |
$198
3,224
kWh
|
- | |
05 | 2.2437: Recover waste heat from equipment | $515 | $1,300 | - |
$515
-
MMBtu
|
|
06 | 2.2525: Eliminate cooling of process streams which subsequently must be heated and vice versa | $4,592 | $27,887 | - |
$4,592
-
MMBtu
|
|
07 | 2.2449: Recover heat from exhausted steam, hot air or hot water | $16,342 | $10,000 | - |
$16,342
-
MMBtu
|
|
TOTAL RECOMMENDED | $32,070 | $54,448 |
$10,621
211,606
kWh
|
$21,449
-
MMBtu
|
||
TOTAL IMPLEMENTED | $10,423 | $14,951 |
$10,423
208,382
kWh
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs