Assessment Year | 1994 |
---|---|
Principal Product | Electromechanical Switches |
NAICS |
n/a
|
SIC | 3643: Current-Carrying Wiring Devices |
Sales Range | $10 M to 50M |
# of Employees | 265 |
Plant Area |
109,433
ft2
|
Annual Production | 8,258,664
pieces
|
Production Hrs. Annual | 6,000
hrs
|
Location (State) | North Carolina |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $424,777 | 7,422,919 |
kWh
|
$0.057 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $50,713 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $32,954 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings |
---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $8,058 | $3,076 |
$8,058
141,852
kWh
|
|
02 | 2.7124: Make a practice of turning off lights when not needed | $5,343 | - |
$5,343
93,787
kWh
|
|
03 | 2.4133: Use most efficient type of electric motors | $8,354 | $10,150 |
$8,354
146,542
kWh
|
|
04 | 2.2511: Insulate bare equipment | $9,405 | $3,536 |
$9,405
165,006
kWh
|
|
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $5,403 | $1,230 |
$5,403
100,234
kWh
|
|
06 | 2.4221: Install compressor air intakes in coolest locations | $1,366 | $750 |
$1,366
24,033
kWh
|
|
07 | 2.7231: Use radiant heater for spot heating | $12,784 | $14,500 |
$12,784
225,967
kWh
|
|
TOTAL RECOMMENDED | $50,713 | $33,242 |
$50,713
897,421
kWh
|
||
TOTAL IMPLEMENTED | $32,954 | $19,556 |
$32,954
585,873
kWh
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs