Assessment Year | 2025 |
---|---|
Principal Product | Integrated Racks |
NAICS | 334419: Other Electronic Component Manufacturing |
SIC | 3672: Printed Circuit Boards |
Sales Range | $100 M to 500M |
# of Employees | 500 |
Plant Area |
844,000
ft2
|
Annual Production | 20,000
units
|
Production Hrs. Annual | 4,680
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $554,353 | 16,456,613 |
kWh
|
$0.034 | |
Electricity Demand | $245,126 | 30,205 |
kW-mo/yr
|
$8.12 | |
Electricity Fees | $124,939 | - |
|
- | |
Natural Gas | $76,791 | 7,909 |
MMBtu
|
$9.71 | |
Waste Disposal Costs | |||||
Water Usage | $768,125 | 33,682 |
Tgal
|
$22.81 | |
TOTAL YEARLY COSTS | $1,769,334 | ||||
RECOMMENDED SAVINGS* | $377,736 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,298 | - |
$1,728
51,269
kWh
|
$570
-
kW-mo/yr
|
- | - | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $11,633 | $5,609 |
$8,769
257,646
kWh
|
$2,864
-
kW-mo/yr
|
- | - | |
03 | 2.1233: Analyze flue gas for proper air/fuel ratio | $998 | $1,346 | - | - | - |
$998
-
MMBtu
|
|
04 | 2.7444: Close holes and openings in building such as broken windows | $13,913 | $73,500 |
$1,795
53,277
kWh
|
$589
-
kW-mo/yr
|
- |
$11,528
-
MMBtu
|
|
05 | 2.4322: Use or replace with energy efficient substitutes | $20,312 | $55,710 |
$14,667
435,212
kWh
|
$5,646
-
kW-mo/yr
|
- | - | |
06 | 2.3212: Optimize plant power factor | $7,122 | $25,622 | - |
$7,122
-
kW-mo/yr
|
- | - | |
07 | 2.8121: Apply for tax-free status for energy purchases | $321,458 | $5,000 | - | - | $321,458 | - | |
TOTAL RECOMMENDED | $377,736 | $166,787 |
$26,959
797,404
kWh
|
$16,792
-
kW-mo/yr
|
$321,458 |
$12,527
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs