Assessment Year | 2024 |
---|---|
Principal Product | gas, electric and wood fireplace |
NAICS | 332510: Hardware Manufacturing |
SIC | 3433: Heating Equipment, Except Electric and Warm Air Furnaces |
Sales Range | $100 M to 500M |
# of Employees | 257 |
Plant Area |
450,000
ft2
|
Annual Production | 101,749
pieces
|
Production Hrs. Annual | 4,000
hrs
|
Location (State) | Iowa |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $276,008 | 6,445,500 |
kWh
|
$0.043 |
Electricity Demand | $407,629 | 20,685 |
kW-mo/yr
|
$19.71 |
Natural Gas | $172,475 | 44,634 |
MMBtu
|
$3.86 |
TOTAL YEARLY COSTS | $856,112 | |||
RECOMMENDED SAVINGS* | $305,514 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $6,949 | $1,000 |
$2,928
68,088
kWh
|
$4,021
-
kW-mo/yr
|
- | - | |
02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $17,558 | $75,320 |
$17,558
408,329
kWh
|
- | - | - | |
03 | 2.4239: Eliminate or reduce compressed air usage | $3,741 | $805 |
$154
3,575
kWh
|
$3,587
-
kW-mo/yr
|
- | - | |
04 | 2.7124: Make a practice of turning off lights when not needed | $96 | $520 |
$96
2,232
kWh
|
- | - | - | |
05 | 2.2622: Replace existing chiller with high efficiency model | $267,134 | $875,396 |
$37,821
879,564
kWh
|
$45,313
-
kW-mo/yr
|
- | $184,000 | |
06 | 2.6231: Utilize controls to operate equipment only when needed | $10,036 | $6,500 | - | - |
$10,036
-
MMBtu
|
- | |
TOTAL RECOMMENDED | $305,514 | $959,541 |
$58,557
1,361,788
kWh
|
$52,921
-
kW-mo/yr
|
$10,036
-
MMBtu
|
$184,000 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs