Assessment Year | 2022 |
---|---|
Principal Product | PVC pipe |
NAICS | 325211: Plastics Material and Resin Manufacturing |
SIC | 2821: Plastics Materials, Synthetic Resins, and Nonvulcanizable Elastomers |
Sales Range | $50 M to 100M |
# of Employees | 31 |
Plant Area |
60,000
ft2
|
Annual Production | 70,000,000
lb
|
Production Hrs. Annual | 8,160
hrs
|
Location (State) | Missouri |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $281,301 | 5,575,128 |
kWh
|
$0.050 | |
Electricity Demand | $196,242 | 9,214 |
kW-mo/yr
|
$21.30 | |
Natural Gas | $81,541 | 41,115 |
MMBtu
|
$1.98 | |
Waste Disposal Costs | |||||
Water Usage | $27,910 | 6,313 |
Tgal
|
$4.42 | |
Water Disposal | $22,718 | 6,313 |
Tgal
|
$3.60 | |
TOTAL YEARLY COSTS | $609,712 | ||||
RECOMMENDED SAVINGS* | $170,841 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $73,208 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $12,571 | $18,580 |
$12,571
251,430
kWh
|
- | - | - | |
02 | 2.9114: Use solar heat to make electricty | $87,851 | $670,334 |
$48,600
972,004
kWh
|
$39,251
-
kW-mo/yr
|
- | - | |
03 | 2.4221: Install compressor air intakes in coolest locations | $1,554 | $7,980 |
$971
18,678
kWh
|
$583
-
kW-mo/yr
|
- | - | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,676 | $1,330 |
$582
11,642
kWh
|
$1,094
-
kW-mo/yr
|
- | - | |
05 | 2.7135: Install occupancy sensors | $506 | $780 |
$506
10,118
kWh
|
- | - | - | |
06 | 2.1233: Analyze flue gas for proper air/fuel ratio | $2,198 | $720 | - | - |
$2,198
-
MMBtu
|
- | |
07 | 3.4116: Meter recycled water (to reduce sewer charges) | $5,524 | $7,544 | - | - | - |
$5,524
-
Tgal
|
|
08 | 2.2622: Replace existing chiller with high efficiency model | $58,961 | $200,000 |
$32,847
656,939
kWh
|
$26,114
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $170,841 | $907,268 |
$96,077
1,920,811
kWh
|
$67,042
-
kW-mo/yr
|
$2,198
-
MMBtu
|
$5,524
-
Tgal
|
||
TOTAL IMPLEMENTED | $73,208 | $219,910 |
$46,000
920,011
kWh
|
$27,208
-
kW-mo/yr
|
- | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs