Assessment Year | 2019 |
---|---|
Principal Product | injectable animal vaccines |
NAICS | 325414: Biological Product (except Diagnostic) Manufacturing |
SIC | 2836: Biological Products, Except Diagnostic Substances |
Sales Range | $100 M to 500M |
# of Employees | 375 |
Plant Area |
301,378
ft2
|
Annual Production | 90,000,000
units
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Missouri |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $1,930,696 | 36,036,006 |
kWh
|
$0.054 | |
Electricity Demand | $689,374 | 76,737 |
kW-mo/yr
|
$8.98 | |
Natural Gas | $411,897 | 139,864 |
MMBtu
|
$2.94 | |
Waste Disposal Costs | |||||
Water Usage | $451,007 | 84,236,020 |
Tgal
|
$0.005 | |
Water Disposal | $627,712 | 84,236 |
Tgal
|
$7.45 | |
TOTAL YEARLY COSTS | $4,110,686 | ||||
RECOMMENDED SAVINGS* | $515,044 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $508,210 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Usage Savings | Water Disposal Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $743 | - |
$605
11,213
kWh
|
$138
-
kW-mo/yr
|
- | - | - | - | |
02 | 2.1233: Analyze flue gas for proper air/fuel ratio | $4,263 | $720 | - | - |
$4,263
-
MMBtu
|
- | - | - | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $102,897 | $152,035 |
$70,915
1,313,246
kWh
|
$16,155
-
kW-mo/yr
|
- | - | - | $15,827 | |
04 | 2.7135: Install occupancy sensors | $25,560 | $24,500 |
$25,560
473,336
kWh
|
- | - | - | - | - | |
05 | 2.3212: Optimize plant power factor | $1,207 | $3,830 | - |
$1,207
-
kW-mo/yr
|
- | - | - | - | |
06 | 2.4221: Install compressor air intakes in coolest locations | $4,884 | $10,920 |
$3,896
72,148
kWh
|
$988
-
kW-mo/yr
|
- | - | - | - | |
07 | 3.4111: Use closed cycle process to minimize waste water production | $375,490 | $148,000 |
$(-1,131.0)
(-20,935)
kWh
|
$(-313.0)
-
kW-mo/yr
|
- |
$157,594
-
Tgal
|
$219,340
-
Tgal
|
- | |
TOTAL RECOMMENDED | $515,044 | $340,005 |
$99,845
1,849,008
kWh
|
$18,175
-
kW-mo/yr
|
$4,263
-
MMBtu
|
$157,594
-
Tgal
|
$219,340
-
Tgal
|
$15,827 | ||
TOTAL IMPLEMENTED | $508,210 | $325,255 |
$95,344
1,765,647
kWh
|
$15,842
-
kW-mo/yr
|
$4,263
-
MMBtu
|
$157,594
-
Tgal
|
$219,340
-
Tgal
|
$15,827 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Usage Savings | Water Disposal Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs