| Assessment Year | 2018 |
|---|---|
| Principal Product | fluid milk, cottage cheese, sour cream |
| NAICS | 311511: Fluid Milk Manufacturing |
| SIC | 2026: Fluid Milk |
| Sales Range | $10 M to 50M |
| # of Employees | 83 |
| Plant Area |
94,000
ft2
|
| Annual Production | 37,500
Tgal
|
| Production Hrs. Annual | 8,760
hrs
|
| Location (State) | Illinois |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $84,967 | 8,008,964 |
kWh
|
$0.011 | |
| Electricity Demand | $130,420 | 15,908 |
kW-mo/yr
|
$8.20 | |
| Natural Gas | $71,969 | 28,693 |
MMBtu
|
$2.51 | |
| Waste Disposal Costs | |||||
| Water Usage | $249,854 | 43,273,000 |
Tgal
|
$0.006 | |
| TOTAL YEARLY COSTS | $537,210 | ||||
| RECOMMENDED SAVINGS* | $55,197 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | $51,162 | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Usage Savings | One-time Revenue or Avoided Cost Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $490 | $2,925 |
$121
10,074
kWh
|
$113
-
kW-mo/yr
|
- | - | $256 | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $869 | $5,414 |
$220
18,326
kWh
|
$206
-
kW-mo/yr
|
- | - | $443 | |
| 03 | 2.7135: Install occupancy sensors | $1,472 | $3,025 |
$775
62,036
kWh
|
$697
-
kW-mo/yr
|
- | - | - | |
| 04 | 2.4221: Install compressor air intakes in coolest locations | $1,225 | $1,800 |
$633
52,751
kWh
|
$592
-
kW-mo/yr
|
- | - | - | |
| 05 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,826 | - |
$944
76,699
kWh
|
$881
-
kW-mo/yr
|
- | - | - | |
| 06 | 2.2511: Insulate bare equipment | $600 | $752 | - | - |
$600
-
MMBtu
|
- | - | |
| 07 | 2.2515: Use optimum thickness insulation | $7,678 | $7,480 |
$3,966
330,501
kWh
|
$3,712
-
kW-mo/yr
|
- | - | - | |
| 08 | 2.1135: Repair furnaces and oven doors so that they seal efficiently | $839 | $1,900 | - | - |
$839
-
MMBtu
|
- | - | |
| 09 | 2.1131: Repair faulty insulation in furnaces, boilers, etc | $1,294 | $5,330 | - | - |
$1,294
-
MMBtu
|
- | - | |
| 10 | 2.4227: Use compressor air filters | $222 | $200 |
$222
18,500
kWh
|
- | - | - | - | |
| 11 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,204 | - |
$455
37,923
kWh
|
$750
-
kW-mo/yr
|
- | - | - | |
| 12 | 3.4151: Minimize water usage | $37,478 | - | - | - | - |
$37,478
-
Tgal
|
- | |
| TOTAL RECOMMENDED | $55,197 | $28,826 |
$7,336
606,810
kWh
|
$6,952
-
kW-mo/yr
|
$2,733
-
MMBtu
|
$37,478
-
Tgal
|
$699 | ||
| TOTAL IMPLEMENTED | $51,162 | $17,462 |
$5,765
478,451
kWh
|
$5,186
-
kW-mo/yr
|
$2,733
-
MMBtu
|
$37,478
-
Tgal
|
- | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Usage Savings | One-time Revenue or Avoided Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs