| Assessment Year | 2018 |
|---|---|
| Principal Product | chimey covers |
| NAICS | 332322: Sheet Metal Work Manufacturing |
| SIC | 3444: Sheet Metal Work |
| Sales Range | $10 M to 50M |
| # of Employees | 80 |
| Plant Area |
122,300
ft2
|
| Annual Production | 440,000
pieces
|
| Production Hrs. Annual | 2,160
hrs
|
| Location (State) | Missouri |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $69,041 | 861,547 |
kWh
|
$0.080 | |
| Electricity Demand | $12,631 | 4,418 |
kW-mo/yr
|
$2.86 | |
| Natural Gas | $66,949 | 7,918 |
MMBtu
|
$8.46 | |
| Waste Disposal Costs | |||||
| Water Usage | $18,239 | 3,839,301 |
Tgal
|
$0.005 | |
| TOTAL YEARLY COSTS | $166,859 | ||||
| RECOMMENDED SAVINGS* | $41,976 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | $12,721 | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Usage Savings | One-time Revenue or Avoided Cost Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 3.4112: Recovery metals from rinse water(evap., ion exchange, ro, electrolysis, electrodialysis) and reuse rinse water | $22,536 | $32,400 |
$(-387.0)
(-4,841)
kWh
|
$(-77.0)
-
kW-mo/yr
|
- |
$1,350
-
Tgal
|
$21,650 | |
| 02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $688 | $75 |
$571
7,139
kWh
|
$117
-
kW-mo/yr
|
- | - | - | |
| 03 | 2.4221: Install compressor air intakes in coolest locations | $862 | $1,160 |
$689
8,618
kWh
|
$173
-
kW-mo/yr
|
- | - | - | |
| 04 | 2.1321: Replace fossil fuel equipment with electrical equipment | $6,719 | $36,000 |
$(-6,480.0)
(-81,000)
kWh
|
$(-2,059.0)
-
kW-mo/yr
|
$15,258
-
MMBtu
|
- | - | |
| 05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,018 | - |
$851
10,635
kWh
|
$167
-
kW-mo/yr
|
- | - | - | |
| 06 | 2.4239: Eliminate or reduce compressed air usage | $10,153 | $6,140 |
$5,563
69,541
kWh
|
$4,590
-
kW-mo/yr
|
- | - | - | |
| TOTAL RECOMMENDED | $41,976 | $75,775 |
$807
10,092
kWh
|
$2,911
-
kW-mo/yr
|
$15,258
-
MMBtu
|
$1,350
-
Tgal
|
$21,650 | ||
| TOTAL IMPLEMENTED | $12,721 | $7,375 |
$7,674
95,933
kWh
|
$5,047
-
kW-mo/yr
|
- | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Usage Savings | One-time Revenue or Avoided Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs