Assessment Year | 2017 |
---|---|
Principal Product | metal food containers |
NAICS | 332431: Metal Can Manufacturing |
SIC | 3411: Metal Cans |
Sales Range | $50 M to 100M |
# of Employees | 142 |
Plant Area |
500,000
ft2
|
Annual Production | 2,190,000,000
pieces
|
Production Hrs. Annual | 8,496
hrs
|
Location (State) | Missouri |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $891,114 | 17,534,617 |
kWh
|
$0.051 | |
Electricity Demand | $270,241 | 27,597 |
kW-mo/yr
|
$9.79 | |
Natural Gas | $572,940 | 161,355 |
MMBtu
|
$3.55 | |
Waste Disposal Costs | |||||
Water Usage | $76,401 | 26,867 |
Tgal
|
$2.84 | |
TOTAL YEARLY COSTS | $1,810,696 | ||||
RECOMMENDED SAVINGS* | $106,029 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $99,373 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $20,566 | - |
$16,121
322,423
kWh
|
$4,445
-
kW-mo/yr
|
- | |
02 | 2.4133: Use most efficient type of electric motors | $6,898 | $46,100 |
$6,398
127,950
kWh
|
$500
-
kW-mo/yr
|
- | |
03 | 2.7135: Install occupancy sensors | $150 | $280 |
$116
2,325
kWh
|
$34
-
kW-mo/yr
|
- | |
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $4,371 | - |
$3,279
65,587
kWh
|
$1,092
-
kW-mo/yr
|
- | |
05 | 2.4227: Use compressor air filters | $2,071 | $900 |
$1,623
32,464
kWh
|
$448
-
kW-mo/yr
|
- | |
06 | 2.4221: Install compressor air intakes in coolest locations | $6,568 | $2,900 |
$4,234
84,669
kWh
|
$2,334
-
kW-mo/yr
|
- | |
07 | 2.4239: Eliminate or reduce compressed air usage | $58,749 | $17,550 |
$46,052
921,031
kWh
|
$12,697
-
kW-mo/yr
|
- | |
08 | 2.2437: Recover waste heat from equipment | $966 | $4,050 | - | - |
$966
-
MMBtu
|
|
09 | 2.9112: Use solar heat to heat water | $5,690 | $96,550 |
$5,690
111,572
kWh
|
- | - | |
TOTAL RECOMMENDED | $106,029 | $168,330 |
$83,513
1,668,021
kWh
|
$21,550
-
kW-mo/yr
|
$966
-
MMBtu
|
||
TOTAL IMPLEMENTED | $99,373 | $67,730 |
$77,823
1,556,449
kWh
|
$21,550
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |