Assessment Year | 2017 |
---|---|
Principal Product | automotive parts and assemblies |
NAICS | 326199: All Other Plastics Product Manufacturing |
SIC | 3714: Motor Vehicle Parts and Accessories |
Sales Range | $10 M to 50M |
# of Employees | 651 |
Plant Area |
350,000
ft2
|
Annual Production | 6,000,000
units
|
Production Hrs. Annual | 4,080
hrs
|
Location (State) | Missouri |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $1,021,089 | 10,584,600 |
kWh
|
$0.096 | |
Electricity Demand | $117,049 | 24,540 |
kW-mo/yr
|
$4.77 | |
Natural Gas | $65,335 | 9,602 |
MMBtu
|
$6.80 | |
Waste Disposal Costs | |||||
Water Usage | $10,725 | 16,182 |
Tgal
|
$0.66 | |
TOTAL YEARLY COSTS | $1,214,197 | ||||
RECOMMENDED SAVINGS* | $209,339 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $136,933 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $326 | - |
$326
3,436
kWh
|
- | - | - | |
02 | 2.2441: Preheat boiler makeup water with waste process heat | $1,238 | $3,570 | - | - |
$1,238
-
MMBtu
|
- | |
03 | 2.2437: Recover waste heat from equipment | $2,547 | $4,050 | - | - |
$2,547
-
MMBtu
|
- | |
04 | 2.4221: Install compressor air intakes in coolest locations | $3,218 | $1,820 |
$2,822
28,223
kWh
|
$396
-
kW-mo/yr
|
- | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $34,321 | $100,150 |
$16,678
173,726
kWh
|
$2,437
-
kW-mo/yr
|
- | $15,206 | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,151 | $4,125 |
$381
3,966
kWh
|
$56
-
kW-mo/yr
|
- | $714 | |
07 | 2.7135: Install occupancy sensors | $658 | $700 |
$658
6,854
kWh
|
- | - | - | |
08 | 2.9112: Use solar heat to heat water | $71,196 | $875,000 |
$62,331
649,277
kWh
|
$4,207
-
kW-mo/yr
|
- | $4,658 | |
09 | 2.4133: Use most efficient type of electric motors | $1,210 | $12,000 |
$1,061
10,609
kWh
|
$149
-
kW-mo/yr
|
- | - | |
10 | 2.7221: Lower temperature during the winter season and vice-versa | $93,474 | $93,474 |
$93,474
973,687
kWh
|
- | - | - | |
TOTAL RECOMMENDED | $209,339 | $1,094,889 |
$177,731
1,849,778
kWh
|
$7,245
-
kW-mo/yr
|
$3,785
-
MMBtu
|
$20,578 | ||
TOTAL IMPLEMENTED | $136,933 | $207,889 |
$114,339
1,189,892
kWh
|
$2,889
-
kW-mo/yr
|
$3,785
-
MMBtu
|
$15,920 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs