| Assessment Year | 2017 |
|---|---|
| Principal Product | plastic food containers |
| NAICS | 326199: All Other Plastics Product Manufacturing |
| SIC | 3089: Plastics Products, Not Elsewhere Classified |
| Sales Range | $100 M to 500M |
| # of Employees | 292 |
| Plant Area |
107,900
ft2
|
| Annual Production | 1,700,000,000
pieces
|
| Production Hrs. Annual | 8,640
hrs
|
| Location (State) | Missouri |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $1,036,153 | 31,219,047 |
kWh
|
$0.033 |
| Electricity Demand | $827,015 | 60,000 |
kW-mo/yr
|
$13.78 |
| Natural Gas | $16,248 | 2,545 |
MMBtu
|
$6.38 |
| TOTAL YEARLY COSTS | $1,879,416 | |||
| RECOMMENDED SAVINGS* | $58,722 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $57,704 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.4133: Use most efficient type of electric motors | $288 | $1,500 |
$288
8,726
kWh
|
- | - | |
| 02 | 2.7135: Install occupancy sensors | $1,018 | $460 |
$555
16,800
kWh
|
$463
-
kW-mo/yr
|
- | |
| 03 | 2.4221: Install compressor air intakes in coolest locations | $10,557 | $3,360 |
$5,953
180,400
kWh
|
$4,604
-
kW-mo/yr
|
- | |
| 04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $16,802 | $37,168 |
$9,969
302,092
kWh
|
$6,833
-
kW-mo/yr
|
- | |
| 05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $24,920 | - |
$24,920
755,153
kWh
|
- | - | |
| 06 | 2.2136: Install / repair insulation on steam lines | $3,843 | $3,460 | - | - |
$3,843
-
MMBtu
|
|
| 07 | 2.7228: Avoid introducing hot, humid, or dirty air into hvac system | $1,295 | $3,460 |
$1,295
39,227
kWh
|
- | - | |
| TOTAL RECOMMENDED | $58,722 | $49,408 |
$42,980
1,302,398
kWh
|
$11,899
-
kW-mo/yr
|
$3,843
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $57,704 | $48,948 |
$42,425
1,285,598
kWh
|
$11,436
-
kW-mo/yr
|
$3,843
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs