Assessment Year | 2015 |
---|---|
Principal Product | Bread, tortilla |
NAICS | 311812: Commercial Bakeries |
SIC | 2045: Prepared Flour Mixes and Doughs |
Sales Range | $50 M to 100M |
# of Employees | 200 |
Plant Area |
150,000
ft2
|
Annual Production | 11,000,000
lb
|
Production Hrs. Annual | 8,600
hrs
|
Location (State) | Missouri |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,018,768 | 16,852,369 |
kWh
|
$0.060 |
Electricity Demand | $449,942 | 33,851 |
kW-mo/yr
|
$13.29 |
Natural Gas | $474,319 | 83,659 |
MMBtu
|
$5.67 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $160,155 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.7425: Clean or color roof to reduce solar load | $8,279 | - |
$6,338
104,835
kWh
|
$1,941
-
kW-mo/yr
|
- | |
02 | 2.4224: Upgrade controls on compressors | $22,758 | $100,000 |
$22,758
376,462
kWh
|
- | - | |
03 | 2.4221: Install compressor air intakes in coolest locations | $16,004 | $6,500 |
$12,242
202,508
kWh
|
$3,762
-
kW-mo/yr
|
- | |
04 | 2.4239: Eliminate or reduce compressed air usage | $1,923 | $1,000 |
$1,471
24,335
kWh
|
$452
-
kW-mo/yr
|
- | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $13,037 | $1,560 |
$9,980
165,082
kWh
|
$3,057
-
kW-mo/yr
|
- | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $62,569 | $115,650 |
$47,882
792,060
kWh
|
$14,687
-
kW-mo/yr
|
- | |
07 | 2.7135: Install occupancy sensors | $30,675 | $7,500 |
$30,675
507,426
kWh
|
- | - | |
08 | 2.1223: Install smaller boiler (increase high fire duty cycle) | $2,330 | $3,500 | - | - |
$2,330
-
MMBtu
|
|
09 | 2.2437: Recover waste heat from equipment | $2,580 | $9,500 | - | - |
$2,580
-
MMBtu
|
|
TOTAL RECOMMENDED | $160,155 | $245,210 |
$131,346
2,172,708
kWh
|
$23,899
-
kW-mo/yr
|
$4,910
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs