Assessment Year | 2015 |
---|---|
Principal Product | electrical insulation |
NAICS | 335999: All Other Miscellaneous Electrical Equipment and Component Manufacturing |
SIC | 3699: Electrical Machinery, Equipment, and Supplies, Not Elsewhere |
Sales Range | $10 M to 50M |
# of Employees | 56 |
Plant Area |
49,832
ft2
|
Annual Production | 4,500,000
pieces
|
Production Hrs. Annual | 4,160
hrs
|
Location (State) | Missouri |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $97,998 | 1,177,360 |
kWh
|
$0.083 |
Electricity Demand | $9,546 | 3,418 |
kW-mo/yr
|
$2.79 |
Natural Gas | $26,680 | 3,750 |
MMBtu
|
$7.11 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $12,217 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $9,841 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,360 | $6,500 |
$1,139
13,728
kWh
|
$221
-
kW-mo/yr
|
|
02 | 2.7135: Install occupancy sensors | $119 | $180 |
$119
1,438
kWh
|
- | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $675 | $900 |
$675
8,129
kWh
|
- | |
04 | 2.6127: Maintain air filters by cleaning or replacement | $617 | $100 |
$617
7,433
kWh
|
- | |
05 | 2.4221: Install compressor air intakes in coolest locations | $2,014 | $1,160 |
$1,892
22,793
kWh
|
$122
-
kW-mo/yr
|
|
06 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,376 | - |
$2,376
28,627
kWh
|
- | |
07 | 2.4133: Use most efficient type of electric motors | $1,419 | $5,868 |
$1,257
15,139
kWh
|
$162
-
kW-mo/yr
|
|
08 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $308 | - |
$273
3,285
kWh
|
$35
-
kW-mo/yr
|
|
09 | 2.4237: Substitute compressed air cooling with water or air cooling | $3,328 | $5,600 |
$3,328
40,096
kWh
|
- | |
TOTAL RECOMMENDED | $12,217 | $20,308 |
$11,676
140,668
kWh
|
$541
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $9,841 | $20,308 |
$9,300
112,041
kWh
|
$541
-
kW-mo/yr
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs