| Assessment Year | 2014 |
|---|---|
| Principal Product | bio-materials, chemicals |
| NAICS | 325411: Medicinal and Botanical Manufacturing |
| SIC | 2899: Chemicals and Chemical Preparations, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 150 |
| Plant Area |
138,000
ft2
|
| Annual Production | 300,000
pieces
|
| Production Hrs. Annual | 3,090
hrs
|
| Location (State) | Missouri |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $616,922 | 9,450,206 |
kWh
|
$0.065 |
| Electricity Demand | $44,788 | 16,488 |
kW-mo/yr
|
$2.72 |
| Natural Gas | $184,585 | 37,440 |
MMBtu
|
$4.93 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $71,280 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $50,662 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.7314: Reduce ventilation air | $14,453 | - |
$6,337
97,041
kWh
|
$226
-
kW-mo/yr
|
$7,890
-
MMBtu
|
|
| 02 | 2.7221: Lower temperature during the winter season and vice-versa | $34,621 | - |
$19,143
293,155
kWh
|
$682
-
kW-mo/yr
|
$14,796
-
MMBtu
|
|
| 03 | 2.4221: Install compressor air intakes in coolest locations | $1,588 | $2,500 |
$1,368
20,946
kWh
|
$220
-
kW-mo/yr
|
- | |
| 04 | 2.7135: Install occupancy sensors | $7,790 | $4,375 |
$7,790
119,294
kWh
|
- | - | |
| 05 | 2.7135: Install occupancy sensors | $12,828 | $3,375 |
$12,828
196,446
kWh
|
- | - | |
| TOTAL RECOMMENDED | $71,280 | $10,250 |
$47,466
726,882
kWh
|
$1,128
-
kW-mo/yr
|
$22,686
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $50,662 | $2,500 |
$26,848
411,142
kWh
|
$1,128
-
kW-mo/yr
|
$22,686
-
MMBtu
|
||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs