Assessment Year 2014
Principal Product glass containers
NAICS 327213: Glass Container Manufacturing
SIC 3221: Glass Containers
Sales Range $10
M
to 50
M
# of Employees 315
Plant Area 354,300
ft2
Annual Production 389,500,000
pieces
Production Hrs. Annual 8,600
hrs
Location (State) Missouri

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $1,858,294 46,051,191
kWh
Electricity Demand $773,608 63,142
kW-mo/yr
Natural Gas $2,485,080 545,602
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $526,892 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $436,367

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings
01 2.3412: Use waste heat to produce steam to drive a steam turbine-generator $89,896 $277,500 $62,995
1,574,875
kWh
$26,901
-
kW-mo/yr
-
02 2.2511: Insulate bare equipment $105,420 $300,000 - - $105,420
-
MMBtu
03 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $192,210 $220,000 $192,210
4,805,250
kWh
- -
04 2.4224: Upgrade controls on compressors $113,101 $200,000 $113,101
2,827,525
kWh
- -
05 2.2437: Recover waste heat from equipment $629 $1,000 - - $629
-
MMBtu
06 2.4239: Eliminate or reduce compressed air usage $17,814 $30,000 $12,485
312,125
kWh
$5,329
-
kW-mo/yr
-
07 2.4111: Utilize energy-efficient belts and other improved mechanisms $4,268 - $4,268
106,707
kWh
- -
08 2.7221: Lower temperature during the winter season and vice-versa $1,868 - $1,058
26,445
kWh
$810
-
kW-mo/yr
-
09 2.7134: Use photocell controls $1,686 $2,450 $1,686
42,140
kWh
- -
TOTAL RECOMMENDED $526,892 $1,030,950 $387,803
9,695,067
kWh
$33,040
-
kW-mo/yr
$106,049
-
MMBtu
TOTAL IMPLEMENTED $436,367 $752,450 $324,808
8,120,192
kWh
$6,139
-
kW-mo/yr
$105,420
-
MMBtu
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs