| Assessment Year | 2026 |
|---|---|
| Principal Product | none |
| NAICS | 712130: Zoos and Botanical Gardens |
| SIC | 8422: Arboreta and Botanical or Zoological Gardens |
| Sales Range | $1 M to 5M |
| # of Employees | 150 |
| Plant Area |
77,507
ft2
|
| Annual Production | 1
units
|
| Production Hrs. Annual | 3,640
hrs
|
| Location (State) | Michigan |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $60,667 | 1,492,967 |
kWh
|
$0.041 |
| Electricity Demand | $129,862 | 3,176 |
kW-mo/yr
|
$40.89 |
| Electricity Fees | $21,443 | - |
|
- |
| Natural Gas | $28,117 | 12,442 |
MMBtu
|
$2.26 |
| Other Energy | $14,011 | 1 |
MMBtu
|
$14,011.00 |
| TOTAL YEARLY COSTS | $254,100 | |||
| RECOMMENDED SAVINGS* | $39,646 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.9114: Use solar heat to make electricty | $25,241 | $220,400 |
$5,887
143,584
kWh
|
$19,355
-
kW-mo/yr
|
- | |
| 02 | 2.7221: Lower temperature during the winter season and vice-versa | $6,408 | - |
$111
2,698
kWh
|
$452
-
kW-mo/yr
|
$5,846
-
MMBtu
|
|
| 03 | 2.1224: Replace boiler | $5,317 | $29,813 | - | - |
$5,317
-
MMBtu
|
|
| 04 | 2.7224: Reduce space conditioning during non-working hours | $715 | $1,128 |
$138
3,348
kWh
|
$561
-
kW-mo/yr
|
$17
-
MMBtu
|
|
| 05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $582 | $1,672 |
$246
5,992
kWh
|
$336
-
kW-mo/yr
|
- | |
| 06 | 2.7446: Utilize sensors controlling roof and wall openings | $578 | $349 | - | - |
$578
-
MMBtu
|
|
| 07 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $377 | $1,633 |
$58
1,407
kWh
|
$320
-
kW-mo/yr
|
- | |
| 08 | 2.4133: Use most efficient type of electric motors | $156 | $805 |
$24
581
kWh
|
$132
-
kW-mo/yr
|
- | |
| 09 | 2.7492: Use proper thickness of insulation on building envelope | $136 | $254 |
$25
603
kWh
|
$82
-
kW-mo/yr
|
$30
-
MMBtu
|
|
| 10 | 2.7135: Install occupancy sensors | $134 | $344 |
$31
762
kWh
|
$103
-
kW-mo/yr
|
- | |
| TOTAL RECOMMENDED | $39,646 | $256,398 |
$6,518
158,974
kWh
|
$21,339
-
kW-mo/yr
|
$11,788
-
MMBtu
|
||
| TOTAL IMPLEMENTED | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs