Assessment Year | 2025 |
---|---|
Principal Product | 0 |
NAICS | 611310: Colleges, Universities, and Professional Schools |
SIC | 7375: Information Retrieval Services |
Sales Range | less than $500 k |
# of Employees | 60 |
Plant Area |
98,257
ft2
|
Annual Production | 1
pieces
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Michigan |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $136,843 | 1,536,290 |
kWh
|
$0.089 | |
Electricity Demand | $106,374 | 4,809 |
kW-mo/yr
|
$22.12 | |
Electricity Fees | $16,030 | - |
|
- | |
Natural Gas | $31,571 | 5,603 |
MMBtu
|
$5.63 | |
Waste Disposal Costs | |||||
Water Usage | $21,985 | 1,256,339 |
Tgal
|
$0.017 | |
TOTAL YEARLY COSTS | $312,803 | ||||
RECOMMENDED SAVINGS* | $30,366 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $10,778 | $16,600 |
$4,862
54,624
kWh
|
$5,916
-
kW-mo/yr
|
- | - | |
02 | 2.3212: Optimize plant power factor | $11,679 | $7,763 | - | - | - | $11,679 | |
03 | 2.1212: Operate boilers on high fire setting | $405 | $1,000 | - | - |
$405
-
MMBtu
|
- | |
04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $313 | $2,395 |
$106
1,190
kWh
|
- |
$207
-
MMBtu
|
- | |
05 | 2.7134: Use photocell controls | $3,442 | $3,932 |
$1,515
17,028
kWh
|
$1,927
-
kW-mo/yr
|
- | - | |
06 | 2.7135: Install occupancy sensors | $986 | $3,228 |
$433
4,867
kWh
|
$553
-
kW-mo/yr
|
- | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,763 | $485 |
$1,215
13,647
kWh
|
$1,548
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $30,366 | $35,403 |
$8,131
91,356
kWh
|
$9,944
-
kW-mo/yr
|
$612
-
MMBtu
|
$11,679 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs