ITAC Assessment: MUCM23
ITAC logo
ITAC Assessment: MUCM23
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 2024
Principal Product N/A
NAICS 611110: Elementary and Secondary Schools
SIC 8211: Elementary and Secondary Schools
Sales Range less than $500
k
# of Employees 280
Plant Area 97,000
ft2
Annual Production 1
units
Production Hrs. Annual 3,570
hrs
Location (State) Michigan

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $108,636 783,002
kWh
Electricity Fees $5,456 -
Natural Gas $23,470 5,859
MMBtu
Other Energy $18,265 1
MMBtu
TOTAL YEARLY COSTS $155,826
RECOMMENDED SAVINGS* $40,093 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Fees Savings Natural Gas Savings One-time Revenue or Avoided Cost Savings
01 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $1,246 $3,407 $1,246
8,900
kWh
- - -
02 2.6125: Keep equipment clean $89 - $89
638
kWh
- - -
03 2.6218: Turn off equipment when not in use $58 - $58
415
kWh
- - -
04 2.7135: Install occupancy sensors $1,319 $3,640 $1,319
9,423
kWh
- - -
05 2.7142: Utilize higher efficiency lamps and/or ballasts $14 $32 $14
96
kWh
- - -
06 2.7221: Lower temperature during the winter season and vice-versa $7,898 - $3,642
26,016
kWh
- $4,256
-
MMBtu
-
07 2.7261: Install timers and/or thermostats $23,125 $1,830 $22,944
163,886
kWh
- $181
-
MMBtu
-
08 2.7291: Reschedule and rearrange multiple-source heating systems $5,208 - $5,208
37,203
kWh
- - -
09 2.8112: Combine utility meters $119 - - - - $119
10 4.821: Pay bills on time to avoid late fees $1,017 - - $1,017 - -
TOTAL RECOMMENDED $40,093 $8,909 $34,521
246,578
kWh
$1,017 $4,436
-
MMBtu
$119
TOTAL IMPLEMENTED - - - - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Fees Savings Natural Gas Savings One-time Revenue or Avoided Cost Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs