Assessment Year 2026
Principal Product Assembles transmission systems for military vehicles
NAICS 336350: Motor Vehicle Transmission and Power Train Parts Manufacturing
SIC 3714: Motor Vehicle Parts and Accessories
Sales Range $10
M
to 50
M
# of Employees 65
Plant Area 110,000
ft2
Annual Production 12
units
Production Hrs. Annual 2,210
hrs
Location (State) Michigan

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $93,731 636,629
kWh
Electricity Fees $10,829 -
Natural Gas $24,290 2,895
MMBtu
Other Gas $1,695 1
MMBtu
TOTAL YEARLY COSTS $130,545
RECOMMENDED SAVINGS* $54,963 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Fees Savings Natural Gas Savings By-product Production Savings
01 2.9114: Use solar heat to make electricty $34,403 $414,720 $28,646
194,868
kWh
- - $5,758
02 2.7221: Lower temperature during the winter season and vice-versa $10,693 - $8,718
59,303
kWh
- $1,976
-
MMBtu
-
03 2.2136: Install / repair insulation on steam lines $87 $45 $87
589
kWh
- - -
04 2.4221: Install compressor air intakes in coolest locations $1,196 $1,924 $1,196
8,136
kWh
- - -
05 2.7134: Use photocell controls $463 $29 $463
3,149
kWh
- - -
06 2.7135: Install occupancy sensors $117 $426 $117
796
kWh
- - -
07 2.7243: Improve air circulation with destratification fans / other methods $2,977 $9,800 $(-668.5)
(-4,548)
kWh
- $3,645
-
MMBtu
-
08 2.8121: Apply for tax-free status for energy purchases $5,028 - - $5,028 - -
TOTAL RECOMMENDED $54,963 $426,944 $38,557
262,293
kWh
$5,028 $5,621
-
MMBtu
$5,758
TOTAL IMPLEMENTED - - - - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Fees Savings Natural Gas Savings By-product Production Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs