| Assessment Year | 2026 |
|---|---|
| Principal Product | Assembles transmission systems for military vehicles |
| NAICS | 336350: Motor Vehicle Transmission and Power Train Parts Manufacturing |
| SIC | 3714: Motor Vehicle Parts and Accessories |
| Sales Range | $10 M to 50M |
| # of Employees | 65 |
| Plant Area |
110,000
ft2
|
| Annual Production | 12
units
|
| Production Hrs. Annual | 2,210
hrs
|
| Location (State) | Michigan |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $93,731 | 636,629 |
kWh
|
$0.15 |
| Electricity Fees | $10,829 | - |
|
- |
| Natural Gas | $24,290 | 2,895 |
MMBtu
|
$8.39 |
| Other Gas | $1,695 | 1 |
MMBtu
|
$1,695.00 |
| TOTAL YEARLY COSTS | $130,545 | |||
| RECOMMENDED SAVINGS* | $54,963 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Fees Savings | Natural Gas Savings | By-product Production Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.9114: Use solar heat to make electricty | $34,403 | $414,720 |
$28,646
194,868
kWh
|
- | - | $5,758 | |
| 02 | 2.7221: Lower temperature during the winter season and vice-versa | $10,693 | - |
$8,718
59,303
kWh
|
- |
$1,976
-
MMBtu
|
- | |
| 03 | 2.2136: Install / repair insulation on steam lines | $87 | $45 |
$87
589
kWh
|
- | - | - | |
| 04 | 2.4221: Install compressor air intakes in coolest locations | $1,196 | $1,924 |
$1,196
8,136
kWh
|
- | - | - | |
| 05 | 2.7134: Use photocell controls | $463 | $29 |
$463
3,149
kWh
|
- | - | - | |
| 06 | 2.7135: Install occupancy sensors | $117 | $426 |
$117
796
kWh
|
- | - | - | |
| 07 | 2.7243: Improve air circulation with destratification fans / other methods | $2,977 | $9,800 |
$(-668.5)
(-4,548)
kWh
|
- |
$3,645
-
MMBtu
|
- | |
| 08 | 2.8121: Apply for tax-free status for energy purchases | $5,028 | - | - | $5,028 | - | - | |
| TOTAL RECOMMENDED | $54,963 | $426,944 |
$38,557
262,293
kWh
|
$5,028 |
$5,621
-
MMBtu
|
$5,758 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Fees Savings | Natural Gas Savings | By-product Production Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs