ITAC Assessment: MU0053
ITAC logo
ITAC Assessment: MU0053
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 2024
Principal Product Polyethylene Film
NAICS 326111: Plastics Bag and Pouch Manufacturing
SIC 2673: Plastics, Foil, and Coated Paper Bags
Sales Range $10
M
to 50
M
# of Employees 135
Plant Area 92,000
ft2
Annual Production 26,280,345
lb
Production Hrs. Annual 8,712
hrs
Location (State) Michigan

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $663,128 9,679,200
kWh
Electricity Demand $238,429 16,067
kW-mo/yr
Electricity Fees $10,866 -
Natural Gas $73,279 8,630
MMBtu
Other Gas $9,300 1
MMBtu
TOTAL YEARLY COSTS $995,003
RECOMMENDED SAVINGS* $109,265 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings
01 2.2136: Install / repair insulation on steam lines $456 $1,958 $244
3,488
kWh
$212
-
kW-mo/yr
-
02 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $439 $51 $316
4,511
kWh
$123
-
kW-mo/yr
-
03 2.4322: Use or replace with energy efficient substitutes $1,429 $4,900 $494
7,057
kWh
$935
-
kW-mo/yr
-
04 2.4322: Use or replace with energy efficient substitutes $79,472 $58,598 $61,516
878,804
kWh
$17,956
-
kW-mo/yr
-
05 2.7261: Install timers and/or thermostats $7,196 $1,904 $5,580
79,719
kWh
$1,616
-
kW-mo/yr
-
06 2.7111: Reduce illumination to minimum necessary levels $955 - $698
9,970
kWh
$257
-
kW-mo/yr
-
07 2.7124: Make a practice of turning off lights when not needed $1,119 - $867
12,379
kWh
$252
-
kW-mo/yr
-
08 2.7135: Install occupancy sensors $865 $512 $672
9,605
kWh
$193
-
kW-mo/yr
-
09 2.7221: Lower temperature during the winter season and vice-versa $90 - $64
911
kWh
$27
-
kW-mo/yr
-
10 2.7243: Improve air circulation with destratification fans / other methods $16,560 $17,565 $16,753
622,833
kWh
$(-192.9)
-
kW-mo/yr
-
11 2.7261: Install timers and/or thermostats $473 $140 $366
5,227
kWh
$107
-
kW-mo/yr
-
12 2.7492: Use proper thickness of insulation on building envelope $210 $546 - - $210
-
MMBtu
TOTAL RECOMMENDED $109,265 $86,174 $87,570
1,634,504
kWh
$21,486
-
kW-mo/yr
$210
-
MMBtu
TOTAL IMPLEMENTED - - - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs