Assessment Year | 2024 |
---|---|
Principal Product | Nickel concentrates and copper concentrates |
NAICS | 212234: Copper Ore and Nickel Ore Mining |
SIC | 1081: Metal Mining Services |
Sales Range | $100 M to 500M |
# of Employees | 150 |
Plant Area |
55,000
ft2
|
Annual Production | 95,000
ton
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Michigan |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $2,092,066 | 31,231,440 |
kWh
|
$0.067 |
Electricity Demand | $163,762 | 52,377 |
kW-mo/yr
|
$3.13 |
Electricity Fees | $334,791 | - |
|
- |
Fuel Oil #1 | $288,149 | 20,676 |
MMBtu
|
$13.94 |
TOTAL YEARLY COSTS | $2,878,768 | |||
RECOMMENDED SAVINGS* | $48,379 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Fuel Oil #1 Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $15,133 | - |
$14,260
203,711
kWh
|
$874
-
kW-mo/yr
|
- | - | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $337 | $17 |
$318
4,536
kWh
|
$19
-
kW-mo/yr
|
- | - | |
03 | 2.4322: Use or replace with energy efficient substitutes | $508 | $1,752 |
$478
6,823
kWh
|
$31
-
kW-mo/yr
|
- | - | |
04 | 2.6211: Conserve energy by efficient use of vending machines | $150 | $400 |
$141
2,015
kWh
|
$9
-
kW-mo/yr
|
- | - | |
05 | 2.7111: Reduce illumination to minimum necessary levels | $1,186 | - |
$1,157
16,533
kWh
|
$29
-
kW-mo/yr
|
- | - | |
06 | 2.7134: Use photocell controls | $84 | $225 |
$79
1,135
kWh
|
$5
-
kW-mo/yr
|
- | - | |
07 | 2.7243: Improve air circulation with destratification fans / other methods | $6,376 | $10,087 |
$(-540.8)
(-7,726)
kWh
|
- | - |
$6,917
-
MMBtu
|
|
08 | 2.7447: Install vinyl strip / high speed / air curtain doors | $14,663 | $5,697 |
$(-521.2)
(-7,446)
kWh
|
$(-180.3)
-
kW-mo/yr
|
- |
$15,365
-
MMBtu
|
|
09 | 4.821: Pay bills on time to avoid late fees | $9,940 | - | - | - | $9,940 | - | |
TOTAL RECOMMENDED | $48,379 | $18,178 |
$15,371
219,581
kWh
|
$786
-
kW-mo/yr
|
$9,940 |
$22,282
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Fuel Oil #1 Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs